Plan Review Notes
Plan Review Notes For Permit 04110381
Permit Number 04110381
Review Stop E
Sequence Number 3
Notes
Date Text
2005-06-07 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP OF
 AHU HEAT.
 PLEASE ALSO SEE 60A OCP FOR 7.5KW.
 MIN 125%
  
 2)NOTE: PLEASE SEE RISER, PLEASE SEE
 MISSING EQUIPMENT GROUNDING CONDUCTOR
 FROM PANEL"A" TO POOL SUB PANEL.
 PLEASE ALSO SEE RISER IS MISSING
 REQUIRED NEUTRAL FOR SAME PANEL.
 250.24,250.110,250.122 ETC.
  
 3)NOTE: PLEASE SEE MANY ITEMS ARE SHOWN
 AS OPTIONAL ON PLANS. PLANS NEED TO
 REFLECT ACTUAL INSTALLATION OF PROJECT.
 ROUGH INSPECTIONS HAVE ALREADY BEEN
 PASSED.
 PLEASE SEE ORIGINAL PLANS WERE STAMPED
 "ALL REVSIONS AND OPTIONS ARE TO BE
 SUBMITTED AND REVIEWED BEFORE ROUGH
 INSPECTION"
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  