2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) THE BIDET REQUIRES A TRAP PER
 SECTION 1002.1
 B) BIDET IS NOT VENTED PER SECTION
 901.2.1. EITHER TIE IN ON THE VENTED
 BLDG BRANCH LINE, TO CONNECT TO A STACK
 VENT.
 2) FAC 61G1-16.003(1) THE SEAL SHALL
 CONTAIN THE NAME OF THE ARCHITECT, AND
 THE REGISTRATION NUMBER, ALONG WITH THE
 WORDS "STATE OF FLORIDA" AND ARCHITECT.
 NONE OF THIS CAN BE SEEN ON THE SEAL.
 FS 481.221
  
  