2004-11-12 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS FOR SOME
 MISSING RECEPTS PER 210.52, 2' OF WALL
 SPACE/
 PLEASE ALSO SEE KITCHEN COUNTERSPACE
 WHICH MAY REQUIRE GFI 12" OR MORE
 210.52C1
  
 2)NOTE: PLEASE SEE HI-HAT LOADS ARE
 BASED ON MAX WATTAGE FOR A FIXTURE.
 MOST RECESSED AIR LOCK CANS ARE 75W
 RATED. 220.3B4
 TYPE OF FIXTURE NOT SUPPLIED, THIS IS
 ONLY A NOTE>
  
 3)NOTE: PLEASE SEE RASIED SEAL IS NOT
 CLEAR AND VISABLE AS REQUIRED UNDER FS
 481.221, FAC 61G1-16
 TRIED TO SHADOW SEAL WITH PENCIL,
 HOWEVER THIS WOULD NOT PROVIDE A CLEAR
 SEAL WITH INFORMATION ON SEAL.
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
  
 PLEASE SEE ONE SET OF PLANS HAS SOME OF
 THE ABOVE ITEMS REDLINED FOR LOCATIONS/
 CLARITY.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.