Plan Review Notes
Plan Review Notes For Permit 04110317
Permit Number 04110317
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00******** UNSAT *******
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE VERIFY # OF CONDUCTORS
 FROM MAIN PANEL TO SUB-PANELS.
 INDICATES
 #6 FOR EQUIPMENT GRNDS?
 250.122
  
 3)NOTE: PLEASE RE-DRAW RISER SO RISER IS
 MORE CLEAR AND VISABLE.
 PLEASE ALSO INCLUDE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS. FBC 104.2.1
  
 4)NOTE: PLEASE SEE 220.31B FOR ADDITION
 OF HEATING LOADS TO SERVICE. HEAT TO BE
 AT 100%.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717