Plan Review Notes For Permit 04110317 |
Permit Number |
04110317 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-11-12 00:00:00 | ******** UNSAT ******* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 2)NOTE: PLEASE VERIFY # OF CONDUCTORS | | FROM MAIN PANEL TO SUB-PANELS. | | INDICATES | | #6 FOR EQUIPMENT GRNDS? | | 250.122 | | | | 3)NOTE: PLEASE RE-DRAW RISER SO RISER IS | | MORE CLEAR AND VISABLE. | | PLEASE ALSO INCLUDE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | PLANS. FBC 104.2.1 | | | | 4)NOTE: PLEASE SEE 220.31B FOR ADDITION | | OF HEATING LOADS TO SERVICE. HEAT TO BE | | AT 100%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|