Plan Review Notes
Plan Review Notes For Permit 04110284
Permit Number 04110284
Review Stop E
Sequence Number 2
Notes
Date Text
2004-12-28 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 NOW COMING BACK IN SEALED BY THE
 ENGINEER, HOWEVER, STAMP FROM ENGINEER
 IS FOR STRUCTURE ONLY.
 ENGINEERS TITLE BLOCK IS NOT COMPLETE
 PER FAC 61G15-23.002 FOR OTHER SHEETS
 ALSO.
  
 **PLEASE UNDERSTAND ELECTRICAL PLANS FOR
 A SF RESIDENCEARE NOT REQUIRED TO BE
 SIGNED AND SEALED BY AN ARCH OR
 ENGINEER, HOWEVER FBC 104.2.1 DOES
 REQUIRE THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 IF THE ENGINEER AS STAMPED ON PLANS IS
 FOR STRUCTUAL, THEN HE IS NOT PERMITTED
 TO SIGN AND SEAL ELECTRICAL PLANS IF NOT
 DONE BY HIM.
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
 ABOUT THIS.
  
 3)NOTE: PLEASE SEE ONE SET OF PLANS HAS
 THE REDLINE DMISSING RECEPTS IN LIVING
 RM PER 210.52
  
 4)NOTE: PLEASE SEE NOTE ON LOWER
 RIGHT-HAND SIDE OF PLANS MENTIONS ARC
 FAULT FOR RECEPTS AND ARC FAULT RECEPTS
 TO BE INSTALLED. PLEASE SEE ARC FAULT
 RECEPTS ARE NOT AVAILABLE AND ARE NOT
 MADE AT THIS TIME.
 SINCE PLANS ARE COMING BACK, PLEASE
 REMOVE NOTE:
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  