Plan Review Notes
Plan Review Notes For Permit 04110284
Permit Number 04110284
Review Stop B
Sequence Number 2
Notes
Date Text
2005-01-04 00:00:00DENIED
  
 1) OWNER/AGENT IS REQUIRED TO SIGN THE
 ENERGY CALC. FORMS ON THE LINE
 PROVIDED.
 THE SECTION ON SHEET ONE OF THE PLANS
 SPECIFIES R-19 INSULATION AND THE ENERGY
 CALC. FORM LISTS R-30. PLEASE CORRECT.
  
 2) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT COVER SHEETS WITH THE FL PRODUCT
 APPROVAL NUMBERS FOR EACH ITEM REQUIRING
 PRODUCT APPROVAL. THIS IS REQUIRED IN
 ADDITION TO MIAMI-DADE NOA.
  
 3) PRODUCT APPROVALS WERE SUBMITTED FOR
 DOUBLE OUTSWING DOORS WHICH ARE
 INCORRECT. SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR SINGLE OUTSWING DOORS.
  
 4) THE INSTALLATION SCHEDULE SUBMITTED
 IS INCORRECT AND NOT COMPLETE. SUBMIT
 (2) TWO COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714