Plan Review Notes For Permit 04110284 |
Permit Number |
04110284 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-11-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 2 SANITARY RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN. | | A) BOTH BATHROOM SHOW TUBS ON THE FLOOR | | PLAN, BUT ONE SHOWS A SHOWER ON THE | | RISER DIAGRAM. | | B) BOTH BATHROOMS SHOW THE TUBS ON THE | | RIGHT SIDE OF THE W/C, BUT THE RISER | | DIAGRAM SHOWS THE TUBS ON THE LEFT SIDE | | OF THE W/C'S. | | C) THE LAVS ARE SHOWN ON THE LEFT SIDE | | OF THE W/C ON THE FLOOR PLAN, BUT ON THE | | RIGHT SIDE OF THE W/C'S ON THE RISER | | DIAGRAM. | | | | PLEASE SEE RED LINE SECTION OF THE RISER | | DIAGRAM FOR EXAMPLE OF HOW THE RISER | | WILL REFLECT THE FLOOR PLAN. | | | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|