2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT 2 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN.
 A) BOTH BATHROOM SHOW TUBS ON THE FLOOR
 PLAN, BUT ONE SHOWS A SHOWER ON THE
 RISER DIAGRAM.
 B) BOTH BATHROOMS SHOW THE TUBS ON THE
 RIGHT SIDE OF THE W/C, BUT THE RISER
 DIAGRAM SHOWS THE TUBS ON THE LEFT SIDE
 OF THE W/C'S.
 C) THE LAVS ARE SHOWN ON THE LEFT SIDE
 OF THE W/C ON THE FLOOR PLAN, BUT ON THE
 RIGHT SIDE OF THE W/C'S ON THE RISER
 DIAGRAM.
  
 PLEASE SEE RED LINE SECTION OF THE RISER
 DIAGRAM FOR EXAMPLE OF HOW THE RISER
 WILL REFLECT THE FLOOR PLAN.
  
  
  