2004-11-12 00:00:00 | ********** UNSAT ************* |
| |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| |
| 2) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| PLEASE ALSO SEE BOTH BATHS NOT SHOWING |
| ANY ELECTRICAL ?? |
| |
| 3)NOTE: PLEASE SEE BOTH BATHS ? 210.70 |
| |
| |
| 4)NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 2002 NEC 210.12 |
| |
| 5)NOTE: PLEASE SEE LIVING RM RECEPT |
| SPACING. 210.52 |
| |
| 6)NOTE: PLEASE SEE FBC 104.2.1, PLANS |
| ARE REQUIRED TO HAVE PRINTED NAME AND |
| SIGNATURE OF PERSON RESPONSIBLE FOR |
| PLANS. |
| PLEASE ALSO SEE TITLE BLOCK AND MISSING |
| INFORMATION PER FAC 61G1-16.004, FS |
| 481.219. |
| ARCH FIRM? FS 481.221 |
| ENG FIRM? FS 471.025,471.023, |
| 61G15-23.002 |
| |
| PLEASE REMOVE ALL OLD/VOIDEDSHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE COPY OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |