2004-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED IN EACH SPACE. ALSO SEE
 SECTION 410.1.
 2) INDICATE THE OCCUPANCY OF EACH UNIT.
 SECTION 104.2.1
 3) DETAIL FOR ACCESSIBLE TOILET ROOM AND
 ACCESSIBLE FIXTURES IS MISSING THE
 FOLLOWING INFORMATION.
 A) 11-4.16.2 CLEAR FLOOR SPACE FOR THE
 WATER CLOSET.
 B) 11-4.16.3 HEIGHT OF THE W/C
 C) 11-4.16.5 FLUSH CONTROLS
 D) 11-4.19.3 CLEAR FLOOR SPACE WITH
 FORWARD APPROACH. SEE FIG.32.
 4) APPLICATION INDICATES EXTERIOR WINDOW
 REPLACEMENT AS THE "DESCRIPTION OF
 PROJECT IN DETAIL" IT APPEARS THAT MORE
 WORK THAN DESCRIBED WILL BE DONE. PLEASE
 SHOW ON THE APPLICATION ALL WORK IN
 DETAIL. ALSO THE VALUATION OF THE WORK
 WILL BE CALCULATED FOR ALL WORK.
 SECTIONS 104.1..1 AND 104.6.5
 6) SUBMIT A BUILDING DRAIN ISOMETRIC
 SHOWING THE POINT OF CONNECTION FOR EACH
 TOILET ROOM. SHOW ALL PIPE SIZING.
 SECTION 104.3.1.1
 7) SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL POINTS OF CONNECTION AND VALVES
 REQUIRED BY SECTION 606.1(4) IF OVERHEAD
 WATER PIPING. SECTION 104.3.1.1
 8) THE FOLLOWING INFORMATIONS IN
 REQUIRED ON THE TITLE BLOCK OF THE
 ARCHITECT OF RECORD. THE FIRM LICENSE
 NUMBER. 61G1-16.004(2) & FS 481.2055
  
  
  