Plan Review Notes
Plan Review Notes For Permit 04110281
Permit Number 04110281
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-16 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS EXTERIOR WINDOW REPLACEMENT,
 YET PLANS SUBMITTED FOR ALL NEW REMODEL
 TENANT SPACE WORK?
  
 IF WORK IS NEW?
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE SHOW/INDICATE SIGNE
 CIRCUITS REQUIRED PER 600.5
  
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE RISER SHOWS WHAT
 APPEARS TO BE A "FUSED" METER/MAIN ?
 PLEASE CLARIFY TYPE OF SERVICE
 EQUIPMENT.
 PLEASE ALSO INCLUDE CONDUCTORS FROM
 METER TO MAIN AND/OR NEW GUTTER.
 215.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717