Plan Review Notes For Permit 04110281 |
Permit Number |
04110281 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-11-16 00:00:00 | ************* UNSAT *********** | | | | 1)NOTE: PLEASE SEE PERMIT APPLICATION | | MENTIONS EXTERIOR WINDOW REPLACEMENT, | | YET PLANS SUBMITTED FOR ALL NEW REMODEL | | TENANT SPACE WORK? | | | | IF WORK IS NEW? | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH A SUBMITTED | | PANEL SCHEDULE(S). | | PLEASE SEE 700.12E FOR CIRCUITING OF | | EM/EXT LTS. | | | | 2)NOTE: PLEASE SHOW/INDICATE SIGNE | | CIRCUITS REQUIRED PER 600.5 | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | | | 4)NOTE: PLEASE SEE RISER SHOWS WHAT | | APPEARS TO BE A "FUSED" METER/MAIN ? | | PLEASE CLARIFY TYPE OF SERVICE | | EQUIPMENT. | | PLEASE ALSO INCLUDE CONDUCTORS FROM | | METER TO MAIN AND/OR NEW GUTTER. | | 215.5 | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER REVIEWERS WHICH MAY HAVE AN AFFECT | | ON ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|