Plan Review Notes
Plan Review Notes For Permit 04110281
Permit Number 04110281
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00BUILDING PLAN REVIEW
 PERMIT:04110281
 ADD: 2600 BROADWAY
 CONT: K&M COMMERCIAL CONTRACTOR
 LLC
 TEL: (561)248-9648 BLD CODE= 2001
 FLORIDA BUILDING CODE * WEST PALM BEACH
 AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THERE
 SEEMS TO BE A DISCREPANCY IN WHAT WORK
 IS TO BE ACCOMPLISHED UNDER THIS
 PERMIT.
 THE APPLICATION INDICATES REPLACEMENT
 OF
 WINDOWS VS PLANS WITH A TENENT FIT UP
 FOR (4) BAYS.
  
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 AGAIN THERE SEEMS TO BE CONFUSION AS TO
  
 WHAT THE CONTRACTOR IS SUBMITTING. THE
 CONTRACTOR HAS SUBMITTED IMPACT RATED
 GLAXING PRODUCT APPROVAL AND WINDOW
 APPROVAL FOR "NON IMPACT" RATED SYSTEM.
 3401.7.2.4 REPLACEMENT OF EXTERIOR
 DOORS
 WINDOWS AND SKYLIGHTS SHALL BE DESIGNED
 AND CONSTRUCTED TO COMPLY WITH CHAPTER
 16 OF THIS CODE. WIND AND LARGE MISSLE
 IMPACT TESTING, EITHER THROUGH GLAZING
 SYSTEM OR STORM SHUTTERS.
  
 4) IN EITHER CASE, REPLACEMENT OF
 GLAZING OR TENANT FIT UP THE PERMIT
 IS VERY, VERY LOW. IF THE TRUE VALUE IS
 NOT SUBMITTED, WE WILL USE MARSHALL &
 SWIFT TO CALCULATE THE PERMIT VALUE.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STORM SHUTTRERS IF NON-IMPACT
 GLAZING IS INSTALLED.
  
 6) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7A) PLANS INDICATE THE REMOVAL OF BLOCK
 BENEATH THE EXISTING WINDOWS WITHOUT
 ANY
  
 VERTICAL NOR HORIZONTAL REINFORCING
 STEEL? EXPLAIN RATIONAL?1707.4.5.2
 MULLIONS SHALL BE DESIGNED TO TRANSFER
 THE DESIGN PRESSURE LOADS APPLIED BY
 THE
 WINDOW OR DOOR ASSEMBLIES TO THE ROUGH
 OPENING SUBTRATE.
 IF THERE IS NO WINDOW SILL HOW WILL
 THIS TRANSFER OF LOADS OCCUR?
 7B) PLANS ALSO INDICATE INFILL AT THE
 WINDOWS AT VARIOUS OPENINGS, NO
 COLUMNS?
 EXPLAIN RATIONAL?
  
 8) PLANS INDICATE THEY COMPLY WITH THE
 CURRENT REQUIREMENTS OF AMERICANS WITH
 DISABILITIES ACT. PLANS SHOULD READ
 FLORIDA AMERICANS WITH DISABILITES &
 ACCESSIBILITY IMPLENTATION ACT
 553.501-553.513.
  
 9) PLANS DO NOT INDICATE THE LENGHT OF
 THE GRAB BARS NOR POSITIONING OF THE
 GRAB BARS BEHIND THE WATER CLOSET.
  
 10) PROVIDE WHAT TYPE OF OCCUPANCY WILL
 OCCUR IN THESE UNITS ?
  
  
 11)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026