2004-11-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT 3.1 SHOW CLEAR FLOOR SPACE FOR |
| FIXTURES IN THE TOILET ROOMS, AND THE |
| TURNING AREA FOR EACH ROOM. SECTIONS |
| 11-4.16.2, 11-4.19.3, AND 11-4.22.3 |
| 2) SHT 8.1 SHOW THE MEASURMENT OFF THE |
| WALL TO THE CENTERLINE OF THE WATER |
| CLOSET AS 18 INCHES AND THE CENTERLINE |
| OF THE LAV AS 15 INCHES MIN. FIGURE 28 |
| AND FIGURE 7(C). |
| 3) SHT 3-1 SHOW FORWARD APPROACH CLEAR |
| FLOOR SPACE FOR THE SINK IN THE SANX |
| ROOM AS REQUIRED IN SECTION 11-4.24.5. |
| SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| SECTIONS 11-4.24.3 KNEE CLEARANCE 27" |
| HIGH, 30" WIDE, AND 19" DEEP PROVIDED |
| UNDERNEATH THE SINK, 11-4.24.4 SINK |
| DEPTH 6-1/2", 11-4.24.5 CLEAR FLOOR |
| SPACE, AND 11-4.24.6 EXPOSED PIPES AND |
| SURFACES, 11-4.24.7 FAUCETS. - PER |
| BUILDING OFFICIAL, DOORS UNDER THE SINK |
| ARE NOT APPROVED AS THEY CREATE AN |
| OBSTRUCTION, THE SPACE UNDER SHALL BE |
| CLEAR FLOOR SPACE. |
| 4) SHT M2 SANITARY RISER ISOMETRIC AND |
| THE PLUMBING PLAN, DELETE THE CLEANOUT |
| LEFT OF THE BUILDING DRAIN DOWNSTREAM OF |
| THE TOILET ROOMS. IT IS NOT REQUIRED AND |
| CAN CREATE A BLOCKAGE AS THE FITTING TO |
| CONNECT THE CLEANOUT TO THE SYSTEM WILL |
| BE AGAINST THE DIRECTION OF FLOW. |
| SECTION 706.3 |
| 5) FULL OPEN VALVES SHALL BE INSTALLED |
| ON THE TOP OF EVERY WATE DOWN-FEED PIPE. |
| SECTION 606.1(4) |
| 6) AN RPZ BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE. SECTION 608.13.2 |
| 7) THERMAL EXPANSION CONTROL IS REQUIRED |
| PER SECTION 607.3.2 |
| |
| |