Plan Review Notes
Plan Review Notes For Permit 04110265
Permit Number 04110265
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 3.1 SHOW CLEAR FLOOR SPACE FOR
 FIXTURES IN THE TOILET ROOMS, AND THE
 TURNING AREA FOR EACH ROOM. SECTIONS
 11-4.16.2, 11-4.19.3, AND 11-4.22.3
 2) SHT 8.1 SHOW THE MEASURMENT OFF THE
 WALL TO THE CENTERLINE OF THE WATER
 CLOSET AS 18 INCHES AND THE CENTERLINE
 OF THE LAV AS 15 INCHES MIN. FIGURE 28
 AND FIGURE 7(C).
 3) SHT 3-1 SHOW FORWARD APPROACH CLEAR
 FLOOR SPACE FOR THE SINK IN THE SANX
 ROOM AS REQUIRED IN SECTION 11-4.24.5.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.24.3 KNEE CLEARANCE 27"
 HIGH, 30" WIDE, AND 19" DEEP PROVIDED
 UNDERNEATH THE SINK, 11-4.24.4 SINK
 DEPTH 6-1/2", 11-4.24.5 CLEAR FLOOR
 SPACE, AND 11-4.24.6 EXPOSED PIPES AND
 SURFACES, 11-4.24.7 FAUCETS. - PER
 BUILDING OFFICIAL, DOORS UNDER THE SINK
 ARE NOT APPROVED AS THEY CREATE AN
 OBSTRUCTION, THE SPACE UNDER SHALL BE
 CLEAR FLOOR SPACE.
 4) SHT M2 SANITARY RISER ISOMETRIC AND
 THE PLUMBING PLAN, DELETE THE CLEANOUT
 LEFT OF THE BUILDING DRAIN DOWNSTREAM OF
 THE TOILET ROOMS. IT IS NOT REQUIRED AND
 CAN CREATE A BLOCKAGE AS THE FITTING TO
 CONNECT THE CLEANOUT TO THE SYSTEM WILL
 BE AGAINST THE DIRECTION OF FLOW.
 SECTION 706.3
 5) FULL OPEN VALVES SHALL BE INSTALLED
 ON THE TOP OF EVERY WATE DOWN-FEED PIPE.
 SECTION 606.1(4)
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 7) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]