2004-12-04 00:00:00DENIED:
 1.PLAN SHEET 3.1 & 8.1 INDICATE THE
 SEPARATION BETWEEN THE WAREHOUSE AND THE
 OFFICE AREA HAS A 2 HR FIRE RATING.
 PLEASE PROVIDE LOCATION AND DETAIL OF
 FIRE DAMPER AS REQUIRED PER 2001 FBC(M)
 607.1.2 & 607.6.
  
 2.PLAN DOES NOT INDICATE CONDENSATE
 TERMINATION, SHOW COMPLIANCE WITH 2001
 FBC(M) 307.2.1 & FBC 1503.4.4.
  
 3.DETAIL OF CONDENSING UNIT SUPPORT ON
 PLAN SHEET 7.1, CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL SHALL COMPLY WITH 2001 FBC
 1511.7.
  