2004-11-15 00:00:00 | REDLINED SEC'S PER 310.16 | | EXST RISER NOTES FPL, YET SEC'S ARE FROM | | WEATHER-HEAD TO METER. | | | | REDLINED POSSIBLE EQUIPMENT GROUNDING | | CONDUCTOR FROM MAIN DISC TO PANEL. | | 250.24,250.122 |
|