Plan Review Notes For Permit 04110260 |
Permit Number |
04110260 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-11-19 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT SPECIFICATIONS FOR THE | | TRANSFER SWITCH FROM THE MFGR. | | | | 2} SUBMIT LOAD CALCULATIONS FOR THE | | LOADS TO BE ENERGIZED BY THE GENERATOR. | | | | 3} SUBMIT TWO CURRENT COPIES OF THE | | PROPERTY SURVEY INDICATING LOCATION OF | | THE GENERATOR AND RELATED EQUIPMENT, FOR | | ZONING REVIEW. | | | | 4} PLEASE INCREASE THE VALUE ON THE | | APPLICATION TO INCLUDE ALL LABOR AND | | MATERIAL, INCLUDING COST OF THE | | GENERATOR AND RELATED EQUIPMEN PER | | 104.6.5 FBC AND CWPB AMMENDMENTS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|