Date |
Text |
2006-05-17 00:00:00 | ******** UNSAT ********* |
| |
| |
| 1) NOTE: PLEASE SEE COMMENTS FROM |
| PREVIOUS REVIEW AS THE SD'S ARE STILL |
| SHOWN BEING WIRED TO MORE THAN ONE |
| CIRCUIT IN A SINGLE UNIT?? |
| PLEASE KNOW, THE SD'S ARE REQUIRED TO |
| WIRED "INLINE", WHICH AS SHOWN ON |
| MULTIPLE CIRCUITS IS NOT PERMITTED. |
| THESE MAY BE WIRED TO THE ARC FAULT |
| PROTECTED BEDRM CIRCUIT, HOWEVEER THESE |
| CAN ONLY BE ON ONE CIRCUIT. |
| NFPA-72 8-1.4.1.6.2, |
| |
| 2) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN |
| DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP |
| SERVICE, AND 4/0'S FOR THE OTHER. |
| PLEASE SEE THAT THE SEC'S SHALL ME SIZED |
| ACCORDINGLY TO THE OCP, HP, AND THE SIZE |
| OF THE FPC. |
| PLEASE SEE 310.16, AS 3/0'S ARE ONLY |
| RATED AT 200A'S AND THE 4/0'S ARE ONLY |
| RATED FOR 225A'S. PLEASE SEE |
| 240.4,310.16. |
| THE OCP SHOWN ON MAIN IS 250A'S. |
| (LOOCKED ROTOR SHOULD BE SET AND PART OF |
| THE FPC AND MUST BE 6X THE FLA'S. |
| 695.4/695.5 |
| |
| ** NOTE ** |
| PLEASE KNOW, IT HAS COME TO THE |
| ATTENTION OF THIS OFFICE THAT SOME OF |
| THE SLIDING GLASS DOORS ON PLANS ARE |
| ACTUALLY "FIXED GLASS PANELS" PLEASE SEE |
| 210.52 AS "FIXED GLASS" IS CONSIDERED |
| WALL SPACE. |
| PLEASE SEE PLANS IN MANY PLACES STILL |
| INDICATE MANY OF THESE AS SLIDING GLASS |
| DOORS?? AS REVIEWED ON PREVIOUS PLANS. |
| ANY INSTALLATION OF FIXED GLASS PANELS, |
| WILL BE VERIFIED IN THE FIELD AND PLANS |
| SHALL BE REVISED ACCORDING TO ACTUAL |
| WALL SPACE CONSTRUCTED. |
| |
| |
| PLEASE REVISE AND SUBMIT THE ABOVE |
| INFORMATION FOR REVIEW. IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-05-16 00:00:00 | NOTES TO FOLLOW. |