Plan Review Notes
Plan Review Notes For Permit 04110185
Permit Number 04110185
Review Stop E
Sequence Number 8
Notes
Date Text
2006-05-17 00:00:00******** UNSAT *********
  
  
 1) NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW AS THE SD'S ARE STILL
 SHOWN BEING WIRED TO MORE THAN ONE
 CIRCUIT IN A SINGLE UNIT??
 PLEASE KNOW, THE SD'S ARE REQUIRED TO
 WIRED "INLINE", WHICH AS SHOWN ON
 MULTIPLE CIRCUITS IS NOT PERMITTED.
 THESE MAY BE WIRED TO THE ARC FAULT
 PROTECTED BEDRM CIRCUIT, HOWEVEER THESE
 CAN ONLY BE ON ONE CIRCUIT.
 NFPA-72 8-1.4.1.6.2,
  
 2) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN
 DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP
 SERVICE, AND 4/0'S FOR THE OTHER.
 PLEASE SEE THAT THE SEC'S SHALL ME SIZED
 ACCORDINGLY TO THE OCP, HP, AND THE SIZE
 OF THE FPC.
 PLEASE SEE 310.16, AS 3/0'S ARE ONLY
 RATED AT 200A'S AND THE 4/0'S ARE ONLY
 RATED FOR 225A'S. PLEASE SEE
 240.4,310.16.
 THE OCP SHOWN ON MAIN IS 250A'S.
 (LOOCKED ROTOR SHOULD BE SET AND PART OF
 THE FPC AND MUST BE 6X THE FLA'S.
 695.4/695.5
  
 ** NOTE **
 PLEASE KNOW, IT HAS COME TO THE
 ATTENTION OF THIS OFFICE THAT SOME OF
 THE SLIDING GLASS DOORS ON PLANS ARE
 ACTUALLY "FIXED GLASS PANELS" PLEASE SEE
 210.52 AS "FIXED GLASS" IS CONSIDERED
 WALL SPACE.
 PLEASE SEE PLANS IN MANY PLACES STILL
 INDICATE MANY OF THESE AS SLIDING GLASS
 DOORS?? AS REVIEWED ON PREVIOUS PLANS.
 ANY INSTALLATION OF FIXED GLASS PANELS,
 WILL BE VERIFIED IN THE FIELD AND PLANS
 SHALL BE REVISED ACCORDING TO ACTUAL
 WALL SPACE CONSTRUCTED.
  
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-05-16 00:00:00NOTES TO FOLLOW.