2005-12-23 00:00:00 | REVISION DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1. SHTS P201, P203, P206, P207, & P208 |
| SHALL BE SUBMITTED FOR REVISION UNDER |
| THE APPROPRIATE PERMIT NUMBER FOR THOSE |
| SHEETS. SECTION 104.2.1. |
| 2. SHTS P205 & 209 REVISION REQUIRED FOR |
| THE ARCHITECTURAL SHEETS SHOWING THE |
| DELETION OF THE SCUPPERS. SEE COMMENT #1 |
| FROM LAST REVISION SUBMITTAL (6-23-5). |
| 3. SHT P210 LEVEL 2-4. LEVEL 2 IS |
| DIFFERENT THAN LEVELS 3 & 4. REVISE |
| SEPARATELY. INDICATE UNIT DESIGNATION ON |
| EACH SHEET. SECTION 104.2.1. |
| - E6 OPP. REVISION REQUIRED FOR THE |
| FLOOR PLAN. ONLY E6 FLOOR PLAN HAS BEEN |
| REVISIED. IF FLOOR PLAN NOT REVISED, |
| SUBMIT A RISER DIAGRAM TO REFLECT |
| UNCHANGED FLOOR PLAN. SECTION 104.3.1.1. |
| - G6 TUB NOT VENTED. WHAT RISER HAS BEEN |
| REVISED TO REFLECT THIS CHANGE? |
| - H6 INDICATE RISER NUMBER TO REFLECT |
| CHANGE. |
| - K6 2ND FLOOR INDICATE RISERS FOR |
| THESE CHANGES. |
| - F6 3RD & 4TH FLOORS |
| 4. SHT P301 WHERE IS WATER HEATER DRAIN |
| PAN - WASTE WATER DETAIL? HAVE THE WATER |
| HEATERS BEEN DELETED? DETAIL TO BE SHOWN |
| ON REVISION. |
| - WHERE IS RISERS SAN/6 & SAN 9? THESE |
| ARE STILL SHOWN ON THE FLOOR PLANS. |
| - SAN/7 DOES NOT REFLECT THE FLOOR |
| PLAN. |
| - UNIT B-2 MASTER BATH SANT FITTINGS |
| SHALL BE INSTALLED TO GUIDE SEWAGE AND |
| WASTE IN THE DIRECTION OF FLOW. SECTION |
| 706.3. |
| - UNIT E-5/6 MASTER BATH, SHOW ALL PIPE |
| SIZES. MAX 4FU ON 2" WET VENT. SECTION |
| 104.2.1 AND TABLE 909.3. |
| |