Plan Review Notes For Permit 04110185 |
Permit Number |
04110185 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-06-23 00:00:00 | REVISION DENIED | | | | 1. SHTS P205 & P209 MORE INFORMATION IS | | REQUIRED FOR REVISION. ARE DOWNSPOUTS | | BEING DELETED? IF SO A REVISION WILL BE | | REQUIRED SHOWING THE DOWNSPOUTS BEING | | DELETED ON THE ARCHITECTURAL SHEETS. | | SECTION 104.2.1. | | 2. SHTS P205 & P209 REVISIONS 2 & 3 WERE | | NOT FOUND. LAST REVISION ON THE STAMPED | | ISSUED SET OF PLANS WAS REVISION 1. | | PLEASE CLOUD AND NUMBER ALL REVISIONS. | | SECTION 104.2.1. | | 3. SHT P207 INDICATE SQUARE FOOTAGE OF | | EACH DOWNSPOUT AND COMBINED SF FOR | | HORIZONTAL SITE STORM LINE WHERE THE 2 | | DOWNSPOUTS ARE NOW CONNECTING TOGETHER. | | ALSO SHOW PIPE SIZE FOR THE HORIZONTAL | | SIET STORM LINE. TABLE 1106.3 (THIS IS | | THE RISER DIAGRAM FOR SHT P209) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|