Plan Review Notes
Plan Review Notes For Permit 04110185
Permit Number 04110185
Review Stop E
Sequence Number 4
Notes
Date Text
2005-12-09 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE NOTE ON ALL PLANS
 INDICATE SD'S ARE TO BE WIRED TO
 HALL/FOYER CIRCUITS, HOWEVER CIRCUITING
 ON PLANS WAS NOT CHANGED.
 PLEASE BE SURE THAT IF THESE SD'S ARE
 NOW GOING TO CHANGE TO HALL/FOYER LTS,
 THEN THESE CIRCUITS WILL ALSO NOW BE
 REQUIRED TO BE ARC FAULT.210.12
 PLEASE ALSO SEE CIRCUITING FOR SD'S HAS
 GONE BACK TO THE SD'S OF THE SAME UNIT
 BEING WIRED TO MORE THAN ONE CIRCUIT.
 SMOKE DETECTORS ARE REQUIRED TO BE WIRED
 INLINE AND THIS WILL NOT WORK ON MORE
 THAN ONE CIRCUIT.
 PLEASE ADJUST ALL CIRCUITING.
  
 2)NOTE: PLEASE SEE FIRE PUMP
 FEEDERS/SEC'S FROM THE FPL TRANSFORMER
 TO THE METER AND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT IS NOTED AS
 HAVING AN EQUIPMENT GROUNDING CONDUCTOR.
 PLEASE REVISE SCHEDULE.
 THESE ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 302 WHICH DOES NOT
 INDICATE ANY REVISONS, HOWEVER TITLE
 BLOCK DOES INDICATE THIS.
  
 4)NOTE: PLEASE SEE 620.23 A SEPARATE
 BRANCH CIRCUIT SHALL SUPPLY THE MACHINE
 ROOM OR CONTROL ROOM/MACHINERY SPACE OR
 CONTROL SPACE LIGHTING AND
 RECEPTACLE(S).
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]