Plan Review Notes
Plan Review Notes For Permit 04110185
Permit Number 04110185
Review Stop E
Sequence Number 3
Notes
Date Text
2005-04-25 00:00:00**REDLINED **
  
 1) NO EQUIPMENT GROUNDING CONDUCTORS
 FROM TRANSFORMER TO METER OR METER TO
 FIRST MEANS OF DISCONNECT.
 250.6,250.24
 EQUIPMENT GROUNDING CONDUCTORS SHOWN TO
 FIRE PUMP SHALL NOT BE INSTALLED.
  
 ALL 12 ROLLS STAMPED FOR ELECTRICAL.
 NO REVISION NEEDED.