2005-02-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW:
 1) A TITLE BLOCK MUST CONTAIN THE
 FOLLOWING INFORMATION.
 61G1-16.004(2)(6)
 THE FIRM LICENSE NUMBER, AND THE
 PRINTED
 NAME OF THE PERSON SEALING THE
 DOCUMENT.
 ALSO THE CERTIFICATE OF AUTHORIZATION
 OF
 THE FIRM. SEE SHEETS L1 THRU L6 AND
 SHEETS I-1 THRU I-3.
 **************NEW COMMENT*************
 1B) SHT P202 BUILDING 1 STORM RISER
 DIAGRAM. MAXIMUM 730 SF @ 1% SLOPE. 4"
 PIPE REQUIRED ON THE HORIZONTAL PIPING
 OR INDICATE 4% SLOPE. INDICATE ON
 PLANS.
 TABLE 1106.3.
 2B) SHT P202 SCUPPERS THRU THE MANSARD
 ROOF REQUIRES A MINIMUM OF 21.195 SQ IN
 6" PIPE IS REQUIRED. TABLE 1106.3 AND
 SECTION 1107.3.
 3B) SHT P204 MINIMUM 4" PIPE REQUIRED
 ON
 STORM RISER HORIZONTAL PIPING. TABLE
 1106.3.
 4B) SHT P204 MINIMUM 6" PIPE REQUIRED
 ON
 THE SCUPPER DRAINS. SECTION 1107.3
  
  
 REVIEW BY KEN STEVENS