Plan Review Notes For Permit 04110185 |
Permit Number |
04110185 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-02-17 00:00:00 | DENIED:BUILDING #3 & 6 | | 1.AS PER CONVERSATION WITH JIM | | MULLENS, DRYER SUBMITTAL TO BE CHANGED | | AND THE PLANS WILL BE REVISED DELETING | | THE BOOSTER FANS INSTALLED IN THE DRYER | | EXHAUST DUCT.SPECIFIC DRYERS ARE TO BE | | INSTALLED BY FINAL INSPECTION. | | | | 2.PLAN SHEET M203 THE TRASH CHUTE ROOM | | DOES NOT INDICATE A CO SENSOR AS | | REQUIRED PER PREVIOUS REVIEW. | | | | 3.PLEASE NOTE, IN THE RESIDENTIAL | | UNITS AS WELL AS COMMON AREAS, SYSTEMS | | THAT HAVE A DESIGN CAPACITY TO PRODUCE | | GREATER THAN 2,000 CFM, DUCT SMOKE | | DETECTORS WILL BE REUQIRED IN THE SUPPLY | | AIR DUCT.AS AN ALTERNATE TO THE DUCT | | SMOKE DUCT DETECTOR, UPON ACTIVATION OF | | AN AREA SMOKE DETECTOR, THE A/C UNIT | | WILL SHUT DOWN.2001 FBC(M)606.2.1, | | 606.2.2, AND 606.4. | | | | 4.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | PER 2001 FBC(M)606.4.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|