2005-02-14 00:00:00 | *** NOTES *** |
| THIS IS FOR BLDGS: 1,2,5 AND 6. |
| THIS COMMENT DOES NOT AFFECT BLDGS: 3 OR |
| 4. |
| |
| 1)NOTE:PLEASE SEE NFPA-20 IN REFERENCE |
| TO FIRE PUMP ELECTRICAL SERVICE |
| LOCATION. |
| PLEASE SEE SERVICE SHALL BE LOCATED AS |
| NOT TO BE AFFECTED IN CASE OF FIRE / |
| EXPLOSION ETC WITH MAIN ELECTRICAL |
| SERVICE. |
| THIS FIRE PUMP SERVICE SHOULD STILL BE |
| LOCATED IN CLOSE PROXIMITY TO MAIN |
| ELECTRICAL RM. |
| PLEASE SEE NFPA-20, 6.2.1 |
| 6-2.1 SERVICE. |
| WHERE POWER IS SUPPLIED BY A SERVICE, IT |
| SHALL BE LOCATED AND ARRANGED TO |
| MINIMIZE THE POSSIBILITY OF DAMAGE BY |
| FIRE FROM WITHIN THE PREMISES AND |
| EXPOSING HAZARDS. |
| NFPA-70 695 |
| THE CONNECTION SHALL BE LOCATED AND |
| ARRANGED SO AS TO MINIMIZE THE |
| POSSIBILITY OF DAMAGE BY FIRE FROM |
| WITHIN THE PREMISES AND FROM EXPOSING |
| HAZARDS. |
| MOST IMPORTANT IN 695.3(A)(2) IS THE |
| REQUIREMENT THAT A FIRE IN ONE SOURCE |
| NOT AFFECT THE RELIABILITY OF ANOTHER |
| SOURCE. |
| |
| THIS WAS NOT IN ORIGINAL REVIEW NOTES. |
| |
| PLEASE MAKE THE ABOVE CHANGES AND SUBMIT |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CONTACTING. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |