Date |
Text |
2004-12-13 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04110185 |
| ADD: 3900 N FLAGLER DR (BLDG 3&6) |
| CONT: MANHATTAN CONSTRUCTION |
| TEL: (813)927-0209 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT |
| NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR |
| SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) THIS PERMIT IS FOR (2) |
| BUILDINGS,(3&6) PROVIDE (2) PERMIT |
| APPLICATIONS, FOR (2) SEPERATE PERMIT |
| THIS WILL BE REQUIRED FOR THE REQUIRED |
| INSPECTION SCHEDULING & TRACKING. |
| 1A) PLANS NEED TO AGREE WITH THE PERMIT |
| APPLICATION. EITHER THE APPLICATION |
| SHOULD BE FOR ONE BUILDING, WITH A |
| FULL NFPA 13 SPRINKLER SYSTEM NOT A 13R |
| AS STATED IN THE FIRE SPRINKLER PLANS |
| OR THERE NEEDS TO BE A 4 HR FIRE WALL |
| SEPERATING THIS STRUCTURE INTO (2) |
| STRUCTUCES, THE SECOND ISSUE WOULD BE |
| TABLE 500, IF A FULL NFPA 13 SUPRESSION |
| SYSTEM IS NOT USED YOU CAN NOT TAKE THE |
| |
| ALLOWABLE HEIGHT INCREASES ALLOWABLE IN |
| TABLE 500 (FOOTNOTE "J"/SEE 903.2. |
| UNTIL THIS ISSUE IS RESOLVED IT WILL BE |
| DIFFICULT TO DETERMINE TABLE 500 |
| ISSUES. |
| |
| 2) PROVIDE SQ. FT. AREAAS OF AREA FOR |
| EACH FLOOR INCLUDE A/C SPACE AND NON- |
| A/C SPACE. |
| |
| 3)AT PARKING SPACES COMPLYING WITH |
| 11-4.1.2(5)(B), PROVIDE MINIMUM VERTICAL |
| CLEARENCE OF 98" AT PARKING SPACES AND |
| ALONG AT LEAST ONE VEHICLE ACCESS ROUTE |
| TO SUCH SPACES FROM SITE ENTRANCES AND |
| EXITS. |
| PROVIDE THE MINIMUM CLEARENCE OF 114" |
| AT ACCESSIBLE PASSENGER LOADING ZONES & |
| AT LEAST 1 VEHICLE ACCESS ROUTE TO SUCH |
| AREAS FROM SITE ENTRANCES & EXITS. |
| |
| 3) NOTE, NOT DISCUSSED UNDER BLDG# 1, |
| IS |
| SITE AMENITIES, GAURD HOUSE, WALLS, |
| WALKWAYS, ETC... REQUIRE A SEPERATE |
| PERMIT. ASSUMED SEAWALL IS ALREADY |
| BUILT, IF NOT A SEPERATE PERMIT IS ALSO |
| REQUIRED, SEE CITY CODE FOR REQUIRED |
| SEAWALL APPROVALS. |
| |
| 4) COMMENTS FROM BLDG# 1 1-33 ALSO |
| PERTAIN TO THIS REVIEW. |
| |
| 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |