Plan Review Notes
Plan Review Notes For Permit 04110184
Permit Number 04110184
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-15 00:00:001. PLEASE INDICATE HOW LONG THE
 SALES TRAILER WILL BE ON-SITE.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 4. WILL THE GUARDHOUSE BE STAFFED
 FULL OR PART TIME. IF PART TIME,
 WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE AND PARAMEDICAL ACCESS.
  
 5. ELECTONIC SWITCHES, CHAIN AND
 LOCKS REQUIRED ON FIRE LINE
 BACKFLOW DEVICES.
  
 6. ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 7. BUILDING ADDRESSES REQUIRED.
  
 8. TACTILE SIGANAGE REQUIRED AT ALL
 EXITS.
  
 9. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 10. KNOX-BOXES WILL BE REQUIRED.
  
 11. A TWO-HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE PARKING AREAS
 AND OTHER PORTIONS OF THE BUILDING
 UNLESS AN EXCEPTION OF NFPA 88A, THE
 STANDARD FOR PARKING STRUCTURES EXISTS.
 OPENING PROTECTIVES SHALL BE AT LEAST
 1 1/2 HOURS.
  
 12. ALL TRASH CHUTES TO COMPLY WITH
 NFPA 82, INCINERATORS, WASTE AND LINEN
 HANDLING SYSTEMS AND EQUIPMENT.
  
 13. ALL BUILDINGS THREE OR MORE STORIES
 IN HEIGHT SHALL BE FIRE SPRINKLER
 PROTECTED IN ACCORDANCE WITH FS 553.895
 (2).
  
 14. STANDPIPE SYSTEMS ARE REQUIRED
 IN ALL BUILDINGS THREE STORIES OR
 THIRTY FEET IN HEIGHT.
  
 15. HOW WILL THE SEPARATE BUILDINGS
 BE IDENTIFIED. WILL THEY BE
 ADDRESSED DIFFERENTLY.
  
 16. 2 1/2 TO 1 1/2 REDUCERS ARE
 REQUIRED AT ALL HOSE VALVE LOCATIONS.
  
 17. FIRE SERVICE MAINS SHOULD BE LOOPED
 WHENEVER POSSIBLE.
  
 18. LOCKING KNOX-BOX CAPS ARE REQUIRED
 ON ALL NEW FIRE DEPARTMENT CONNECTIONS.
  
 19. ALL FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 20. ELEVATOR WARNING SIGNS REQUIRED.
  
 21. EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 22. ADDITIONAL EXIT SIGNS ARE NEEDED
 IN THE GARAGE LEVEL.
  
 23. PLEASE NOTE ON THE PLANS THAT
 SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM A/C
 DIFFUSERS.
  
 24. PLEASE INDICATE ALL LOCATIONS OF
 PORTABLE FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL