2005-12-16 00:00:00****CORRECTIONS****
  
 SUBMITTALS; TENDON AND SUPPORT SHOPS AND
 CALCS
  
 BLDG 1, LEVELS 3 & 4
 BLDG 1, ROOF
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A TITLE BLOCK IS REQUIRED,
 FAC61G15-23.003.MR. HAMID'S ADDRESS ON
 DBPE WEBSITE IS NOT THE ADDRESS ON THE
 PLAN, WHICH APPEARS TO BE FOR PTE.IF
 PTE IS PRACTICING ENGINEERING AND MR.
 HAMID IS THE INDIVIDUAL WHO IS SEALING
 THE DOCUMENT THROUGH THE COMPANY, THE
 INFORMATION FOR PTE SERVES AS THE TITLE
 BLOCK AND IS REQUIRED TO HAVE THE
 CERTIFICATE OF AUTHORIZATION FOR THE
 FIRM PRINTED ON THE PLAN.IF MR. HAMID
 IS SEALING THE PLAN INDIVIDUALLY, HIS
 TITLE BLOCK WITH ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 IS REQUIRED.