Plan Review Notes
Plan Review Notes For Permit 04110183
Permit Number 04110183
Review Stop P
Sequence Number 4
Notes
Date Text
2005-11-15 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHTS P203, P205, P206, P207, P208,
 P209, 7 P210 SHALL BE SUBMITTED FOR
 REVISION UNDER THE APPROPRIATE PERMIT
 NUMBER FOR THOSE SHEETS. SECTION
 104.2.1.
 2. SHTS P205 & 209 REVISION REQUIRED FOR
 THE ARCHITECTURAL SHEETS SHOWING THE
 DELETION OF THE SCUPPERS. SEE COMMENT #1
 FROM LAST REVISION SUBMITTAL (6-23-5).
 3. SHT P210 LEVEL 2-4. LEVEL 2 IS
 DIFFERENT THAN LEVELS 3 & 4. REVISE
 SEPARATELY. INDICATE UNIT DESIGNATION ON
 EACH SHEET. SECTION 104.2.1.
 - E6 OPP. REVISION REQUIRED FOR THE
 FLOOR PLAN. ONLY E6 FLOOR PLAN HAS BEEN
 REVISIED. IF FLOOR PLAN NOT REVISED,
 SUBMIT A RISER DIAGRAM TO REFLECT
 UNCHANGED FLOOR PLAN. SECTION 104.3.1.1.
 - G6 TUB NOT VENTED. WHAT RISER HAS BEEN
 REVISED TO REFLECT THIS CHANGE?
 - H6 INDICATE RISER NUMBER TO REFLECT
 CHANGE.
 - K6 2ND FLOOR INDICATE RISERS FOR
 THESE CHANGES.
 - F6 3RD & 4TH FLOORS
 4. SHT P301 WHERE IS WATER HEATER DRAIN
 PAN - WASTE WATER DETAIL? HAVE THE WATER
 HEATERS BEEN DELETED? DETAIL TO BE SHOWN
 ON REVISION.
 - WHERE IS RISERS SAN/6 & SAN/9? THESE
 ARE STILL SHOWN ON THE FLOOR PLANS.
 - SAN/7 DOES NOT REFLECT THE FLOOR
 PLAN.
 - UNIT B-2 MASTER BATH SANT FITTINGS
 SHALL BE INSTALLED TO GUIDE SEWAGE AND
 WASTE IN THE DIRECTION OF FLOW. SECTION
 706.3.
 - UNIT E-5/6 MASTER BATH, SHOW ALL PIPE
 SIZES. MAX 4FU ON 2" WET VENT. SECTION
 104.2.1 AND TABLE 909.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  