Plan Review Notes
Plan Review Notes For Permit 04110183
Permit Number 04110183
Review Stop M
Sequence Number 4
Notes
Date Text
2006-01-04 00:00:00DENIED: PERMIT 04110183
 PLANS INDICATE VE FOR VARIOUS AHU'S TO A
 LESSER TONNAGE/BTU'S.ENERGY &MANUAL
 J CALCULATIONS HAVE NOT BEEN REVISED.
 PLEASE CLARIFY MANUFACTURER REQUIREMENT
 FOR SIZING OF THE LINE SETS.
  
 PLANS INDICATE THE FOLLOWING CHANGES:
 PLAN SHEET M-201 UNIT A1
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-5 (4 TON) REPLACING AHU-6 (5 TON)
  
 PLAN SHEET M203 UNIT C2
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-2 (2.5 TON) REPLACING AHU-3 (3 TON)
  
 PLAN SHEET M205 UNIT C3
 AHU-4 (3.5 TON) REPLACING AHU-5 (4 TON)
 AHU-7 (1.5 TON ) REPLACING AHU-1 (2 TON)
  
 PLAN SHEET M206 UNIT A4
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-5 (4 TON) REPLACING AHU-6 (5 TON)
  
 PLAN SHEET M208UNITS E5 & D-5
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-3 (3 TON) REPLACING AHU-4 (3.5 TON)
 AHU-7 (1.5 TON)REPLACING AHU-1(2 TON)
  
 PLAN SHEET M210 UNITS F6, E6, & D6
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-3 (3 TON) REPLACING AHU-4 (3.5 TON)
 AHU-7 (1.5 TON) REPLACING AHU-1 (2 TON)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.