2005-12-09 00:00:00 | ****** UNSAT ******* |
| |
| 1)NOTE: PLEASE SEE NOTE ON ALL PLANS |
| INDICATE SD'S ARE TO BE WIRED TO |
| HALL/FOYER CIRCUITS, HOWEVER CIRCUITING |
| ON PLANS WAS NOT CHANGED. |
| PLEASE BE SURE THAT IF THESE SD'S ARE |
| NOW GOING TO CHANGE TO HALL/FOYER LTS, |
| THEN THESE CIRCUITS WILL ALSO NOW BE |
| REQUIRED TO BE ARC FAULT.210.12 |
| PLEASE ALSO SEE CIRCUITING FOR SD'S HAS |
| GONE BACK TO THE SD'S OF THE SAME UNIT |
| BEING WIRED TO MORE THAN ONE CIRCUIT. |
| SMOKE DETECTORS ARE REQUIRED TO BE WIRED |
| INLINE AND THIS WILL NOT WORK ON MORE |
| THAN ONE CIRCUIT. |
| PLEASE ADJUST ALL CIRCUITING. |
| |
| 2)NOTE: PLEASE SEE FIRE PUMP |
| FEEDERS/SEC'S FROM THE FPL TRANSFORMER |
| TO THE METER AND FROM THE METER TO THE |
| FIRST MEANS OF DISCONNECT IS NOTED AS |
| HAVING AN EQUIPMENT GROUNDING CONDUCTOR. |
| PLEASE REVISE SCHEDULE. |
| THESE ARE ONLY INSTALLED AFTER THE FIRST |
| MEANS OF DISCONNECT. |
| |
| 3)NOTE: PLEASE SEE 302 WHICH DOES NOT |
| INDICATE ANY REVISONS, HOWEVER TITLE |
| BLOCK DOES INDICATE THIS. |
| |
| 4)NOTE: PLEASE SEE 620.23 A SEPARATE |
| BRANCH CIRCUIT SHALL SUPPLY THE MACHINE |
| ROOM OR CONTROL ROOM/MACHINERY SPACE OR |
| CONTROL SPACE LIGHTING AND |
| RECEPTACLE(S). |
| |
| PLEASE MAKE THE ABOVE CORRECTIONS AND |
| SUBMIT FOR REVIEW. IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |