Plan Review Notes
Plan Review Notes For Permit 04110183
Permit Number 04110183
Review Stop M
Sequence Number 3
Notes
Date Text
2005-05-20 00:00:00PROVISO:
 SYSTEMS THAT HAVE THE DESIGN CAPACITY (5
 TON & LARGER), GRATER THAN 2,000 CFM
 SHALL HAVE FANSHUT DOWN BY DUCT SMOKE
 DETECTOR OR THE SYSTEM IS PROTECTED BY
 AREA SMOKE DETECTORS IN ACCORDANCE WITH
 2001 FBC/M 606.4.
  
 DRYERS ARE TO BE INSATLLED FOR FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  