Plan Review Notes For Permit 04110183 |
Permit Number |
04110183 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-02-17 00:00:00 | DENIED:BUILDING #1 | | 1.AS PER CONVERSATION WITH JIM | | MULLENS, DRYER SUBMITTAL TO BE CHANGED | | AND THE PLANS WILL BE REVISED DELETING | | THE BOOSTER FANS INSTALLED IN THE DRYER | | EXHAUST DUCT.SPECIFIC DRYERS ARE TO BE | | INSTALLED BY FINAL INSPECTION. | | | | 2.PLAN SHEET M203 THE TRASH CHUTE ROOM | | DOES NOT INIDCATE A CO SENSOR AS | | REQUIRED PER PREVIOUS REVIEW. | | | | 3.PLEASE NOTE, IN THE RESIDENTIAL | | UNITS AS WELL AS COMMON AREAS, SYSTEMS | | THAT HAVE THE DESIGN CAPACITY TO PRODUCE | | GREATER THAN 2,000 CFM, DUCT SMOKE | | DETECTORS WILL BE REQUIRED IN THE SUPPLY | | AIR DUCT.AS AN ALTERNATE TO THE DUCT | | SMOKE DETECTOR, UPON ACTIVATION OF AN | | AREA DUCT SMOKE DETECTOR, THE A/C UNIT | | WILL SHUT DOWN.2001 FBC(M) 606.2.1, | | 606.2.2 AND 606.4. | | | | 4.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | PER 2001 FBC(M)606.4.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|