Plan Review Notes
Plan Review Notes For Permit 04110183
Permit Number 04110183
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-14 00:00:00*** NOTES ***
 THIS IS FOR BLDGS: 1,2,5 AND 6.
 THIS COMMENT DOES NOT AFFECT BLDGS: 3 OR
 4.
  
 1)NOTE:PLEASE SEE NFPA-20 IN REFERENCE
 TO FIRE PUMP ELECTRICAL SERVICE
 LOCATION.
 PLEASE SEE SERVICE SHALL BE LOCATED AS
 NOT TO BE AFFECTED IN CASE OF FIRE /
 EXPLOSION ETC WITH MAIN ELECTRICAL
 SERVICE.
 THIS FIRE PUMP SERVICE SHOULD STILL BE
 LOCATED IN CLOSE PROXIMITY TO MAIN
 ELECTRICAL RM.
 PLEASE SEE NFPA-20, 6.2.1
 6-2.1 SERVICE.
 WHERE POWER IS SUPPLIED BY A SERVICE, IT
 SHALL BE LOCATED AND ARRANGED TO
 MINIMIZE THE POSSIBILITY OF DAMAGE BY
 FIRE FROM WITHIN THE PREMISES AND
 EXPOSING HAZARDS.
 NFPA-70 695
 THE CONNECTION SHALL BE LOCATED AND
 ARRANGED SO AS TO MINIMIZE THE
 POSSIBILITY OF DAMAGE BY FIRE FROM
 WITHIN THE PREMISES AND FROM EXPOSING
 HAZARDS.
 MOST IMPORTANT IN 695.3(A)(2) IS THE
 REQUIREMENT THAT A FIRE IN ONE SOURCE
 NOT AFFECT THE RELIABILITY OF ANOTHER
 SOURCE.
  
 THIS WAS NOT IN ORIGINAL REVIEW NOTES.
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CONTACTING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]