2005-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110183
 ADD: 3900 N FLAGLER DR. BLDG# 1
 CONT: MANHATTEN CONSTRUCTION
 TEL: (813)927-0209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENT #1 FROM THE PREVIOUS REVIEW,
 PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT #7 FROM THE PREVIOUS REVIEW,
 A202, DEALS WITH LISTING THE DOOR RATING
 IN EITHER MINUTES OR HRS. THE HEADING OF
 THIS COLULM STILL INDICATE DOOR "LABEL"
 THE SECOND ISSUE IS THE BUILDINGS
 WITH THE DOORS OF THE TERMINATION ROOM
 THAT ARE ON THE EXTERIOR OF THE BUILDING
  
 HAVE NO RATING. SEE TABLE 705.1.2.
  
 3) COMMENT #8 FROM THE PREVIOUS REVIEW,
 TRASH CHUTE A503 IS TO INDICATE A 2HR
 RATING THROUGH TO THE UNDERSIDE OF THE
 ROOF SHEATHING,THE RATING IS MISSING
 AT THE BOTTOM OF THE TRUSSES, SEE
 705.2.3.4.2.
  
 4) COMMENT #17 FROM THE PREVIOUS REVIEW,
 A502 PROVIDE INFO FOR ACCESS HATCH,
 HATCH DOES NOT NEED TO BE 2 HR RATING
 SINCE IT IS NO LONGER PART OF THE SHAFT.
  
 5)COMMENT # 23 FROM THE PREVIOUS REVIEW,
 1503.4.2 OVERFLOW DRAINS SHALL BE THE
 SAME SIZE AS ROOF DRAINS, INSTALLED WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
 THE EMERGENCY OVERFLOW DRAIN IS
 INDICATED ON THE "P" SHEETS BUT THE
 HEIGHT FROM THE ROOF LINE IS NOT
 INDICATED, IT COULD BE 6" ABOVE THE ROOF
 DRAIN. THE INTENT IS NOT TO HAVE OVER 4"
  
 OF WATER ON THE ROOF. WITH THE SLOPED
 ROOF SYSTEM IF THE EMERGENCY DRAIN IS
 LEVEL WITH THE ROOF LINE YOU WILL HAVE A
 MAXIMUM OF 4"OF WATER AT THE ROOF
 DRAIN.
  
 6)COMMENT #24 FROM THE PREVIOUS REVIEW,
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
 THE PLUMBING PAGES SHOW COMPLIANCE
 WITH SPLASH BLOCKS FOR DOWN SPOUTS, BUT
 THE MECHANICAL DOESN'T INDICATE
 COMPLIANCE FOR CONDENSATE DRAINS.
  
 7)COMMENT #25 FROM THE PREVIOUS REVIEW,
 BUILDING # 1 SHOWS COMPLIANCE, BUT THE
 OTHER BUILDINGS DO NOT HAVE ANYNOTES
 OR DETAIL INDICATING COMPLIANCE.
 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 8)COMMENT #26 MEAN ROOF HEIGHT IS ABOVE
 35', THE WEST PALM AMENDMENTS ARE GOOD
 TO 35', ENGINEER TO INDICATE NAILING
 PATTERNS FOR ABOVE 35'. TABLE 2306.1*
  
 9)COMMENT #27 FROM THE PREVIOUS REVIEW,
 THE STRUCTURAL PLANS DO NOT PROVIDE A
 ROOF FRAMING PLAN WITH THE TRUSSES
 IDENTIED, NOR THE LOADS TO BE IMPOSED,
 UPLIFT, GRAVITY NOR F1OR F2. THE ROOF
 TRUSSES ARE PART OF THE MAIN WIND FORCE
 RESISTING SYSTEM FOR THE STRUCTURE.
 THESE LOADS NEED TO BE IDENTIFIED TO
 ALLOW FOR THE CORRECT ANCHORS TO BE
 EMBEDDED INTO THE CONCRETE POUR. SEE
 FBC 1606.2.4
  
 10)COMMENT # 28 FROM THE PREVIOUS REVIEW
 THERE IS NO ANCHOR SCHEDULE IDENTIFYING
 THE MANUFACTURER, MODEL NUMBER, AND THE
 ALLOWABLE LOADSFOR ANCHORS THAT ARE
 PRINTED IN THE MANUFACTURERS 2005
 CATALOG.
  
 11)COMMENT #28C) FROM THE PREVIOUS
 REVIEW, SHEAT S9-1 "SEE LATEST SIMPSON
 CATALOG FOR FASTENER REQUIREMENTS
 CORRESPONDING TO SIMSON CONNECTORS
 SPECIFIED. THE DESIGN PROFESSIONAL
 HASN,T GIVEN ANY VALUES FOR UPLIFT OR
 OTHER VALUES OF RESISTANCE. NOR HAS THE
 DESIGN PROFESSIONAL PROVIDED A ANCHOR
 SCHEDULE INDICATING WHAT VALUES THAT
 THEY PREFER TO USE.104.2.1 W.P.B.
 ADMINISTRATIVE CODE DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 12) COMMENT #29A) FROM THE PREVIOUS
 REVIEW. A-451 DETAIL #4, THE ATTACHMENT
 OF THE FOAM BRAKET,PLANS DO NOT
 PROVIDE WHAT TYPE OF ATTACHMENT METHOD
 TO BE USED OR QUANITITY OF FASTENERS.
  
 13) COMMENT #30 FROM THE PREVIOUS REVIEW
 A442 DETAIL #8, THE BAHAMA SHUTTER IS TO
 BE ATTACHED TO A 2X_, THE SHUTTER
 PRODUCT APPROVAL PROVIDES FASTENERS FOR
 THE SHUTTER BUT THE DETAIL LACKS HOW
 THE FRAMING MEMBER IS ATTACHED TO THE
 STRUCTURE. FASTENER, SIZE & SPACING.
  
 14) COMMENT #32 FROM THE PEVIOUS REVIEW,
 PROVIDE UNITITY OF TITLE FOR LOTS:
 74-43-43-09-01-000-0110
 74-43-43-09-01-000-0090
  
 15) COMMENT #31 FROM THE PEVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THESE COMMENTS MAY OR MAY NOT PERTAIN TO
 BUILDING #1 SINCE THE PLANS HAVE ALL
 BUILDINGS COMBINED, OTHER COMMENTS MAY
 APPEAR THAT WERE NOT PART OF THE
 PREVIOUS REVIEW SINCE ALL BUILDINGS ARE
 INCORPORATED INTO ONE PLAN. PLEASE BREAK
 THE MEP INTO A SINGLE UNIT, PLANS ARE TO
 CUMBERSOME TO REVIEW AS IS,
  
 *********NOTE*******NOT ALL ROLLS OF
 PLANS ARE COMPLETE,SOME ARE MISSING
 THE STRUCTURAL PAGES TOTALLY.
  
 *********NOTE******PRODUCT APPROVALS (3)
 SETS OF PRODUCT APPROVALS WILL BE
 REQUIRED FOR PROJECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  