2005-02-11 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04110183 |
| ADD: 3900 N FLAGLER DR. BLDG# 1 |
| CONT: MANHATTEN CONSTRUCTION |
| TEL: (813)927-0209 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) COMMENT #1 FROM THE PREVIOUS REVIEW, |
| PROVIDE NOC RECORDED WITH THE CLERK OF |
| COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) COMMENT #7 FROM THE PREVIOUS REVIEW, |
| A202, DEALS WITH LISTING THE DOOR RATING |
| IN EITHER MINUTES OR HRS. THE HEADING OF |
| THIS COLULM STILL INDICATE DOOR "LABEL" |
| THE SECOND ISSUE IS THE BUILDINGS |
| WITH THE DOORS OF THE TERMINATION ROOM |
| THAT ARE ON THE EXTERIOR OF THE BUILDING |
| |
| HAVE NO RATING. SEE TABLE 705.1.2. |
| |
| 3) COMMENT #8 FROM THE PREVIOUS REVIEW, |
| TRASH CHUTE A503 IS TO INDICATE A 2HR |
| RATING THROUGH TO THE UNDERSIDE OF THE |
| ROOF SHEATHING,THE RATING IS MISSING |
| AT THE BOTTOM OF THE TRUSSES, SEE |
| 705.2.3.4.2. |
| |
| 4) COMMENT #17 FROM THE PREVIOUS REVIEW, |
| A502 PROVIDE INFO FOR ACCESS HATCH, |
| HATCH DOES NOT NEED TO BE 2 HR RATING |
| SINCE IT IS NO LONGER PART OF THE SHAFT. |
| |
| 5)COMMENT # 23 FROM THE PREVIOUS REVIEW, |
| 1503.4.2 OVERFLOW DRAINS SHALL BE THE |
| SAME SIZE AS ROOF DRAINS, INSTALLED WITH |
| THE INLET FLOW LINE LOCATED 2" ABOVE THE |
| LOWEST POINT OF THE ROOF LINE. OVERFLOW |
| SCUPPERS SHALL BE A MINIMUM OF 4"IN |
| HEIGTH AND SHALL BE PLACED IN WALLS OR |
| PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| THE EMERGENCY OVERFLOW DRAIN IS |
| INDICATED ON THE "P" SHEETS BUT THE |
| HEIGHT FROM THE ROOF LINE IS NOT |
| INDICATED, IT COULD BE 6" ABOVE THE ROOF |
| DRAIN. THE INTENT IS NOT TO HAVE OVER 4" |
| |
| OF WATER ON THE ROOF. WITH THE SLOPED |
| ROOF SYSTEM IF THE EMERGENCY DRAIN IS |
| LEVEL WITH THE ROOF LINE YOU WILL HAVE A |
| MAXIMUM OF 4"OF WATER AT THE ROOF |
| DRAIN. |
| |
| 6)COMMENT #24 FROM THE PREVIOUS REVIEW, |
| 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| THE PLUMBING PAGES SHOW COMPLIANCE |
| WITH SPLASH BLOCKS FOR DOWN SPOUTS, BUT |
| THE MECHANICAL DOESN'T INDICATE |
| COMPLIANCE FOR CONDENSATE DRAINS. |
| |
| 7)COMMENT #25 FROM THE PREVIOUS REVIEW, |
| BUILDING # 1 SHOWS COMPLIANCE, BUT THE |
| OTHER BUILDINGS DO NOT HAVE ANYNOTES |
| OR DETAIL INDICATING COMPLIANCE. |
| 1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| MECH. 301.13 WIND RESISTANCE MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| ARE EXPOSED TO WIND SHALL BE DESIGNED |
| AND INSTALLED TO RESIST THE WIND |
| PRESSURES ON THE EQUIPMENT & THE |
| SUPPORTS AS DETERMINED IN ACCORDANCE |
| WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| LISHED BY DESIGN OR BY APPLICATION OF |
| SECTION 301.13.1. |
| |
| 8)COMMENT #26 MEAN ROOF HEIGHT IS ABOVE |
| 35', THE WEST PALM AMENDMENTS ARE GOOD |
| TO 35', ENGINEER TO INDICATE NAILING |
| PATTERNS FOR ABOVE 35'. TABLE 2306.1* |
| |
| 9)COMMENT #27 FROM THE PREVIOUS REVIEW, |
| THE STRUCTURAL PLANS DO NOT PROVIDE A |
| ROOF FRAMING PLAN WITH THE TRUSSES |
| IDENTIED, NOR THE LOADS TO BE IMPOSED, |
| UPLIFT, GRAVITY NOR F1OR F2. THE ROOF |
| TRUSSES ARE PART OF THE MAIN WIND FORCE |
| RESISTING SYSTEM FOR THE STRUCTURE. |
| THESE LOADS NEED TO BE IDENTIFIED TO |
| ALLOW FOR THE CORRECT ANCHORS TO BE |
| EMBEDDED INTO THE CONCRETE POUR. SEE |
| FBC 1606.2.4 |
| |
| 10)COMMENT # 28 FROM THE PREVIOUS REVIEW |
| THERE IS NO ANCHOR SCHEDULE IDENTIFYING |
| THE MANUFACTURER, MODEL NUMBER, AND THE |
| ALLOWABLE LOADSFOR ANCHORS THAT ARE |
| PRINTED IN THE MANUFACTURERS 2005 |
| CATALOG. |
| |
| 11)COMMENT #28C) FROM THE PREVIOUS |
| REVIEW, SHEAT S9-1 "SEE LATEST SIMPSON |
| CATALOG FOR FASTENER REQUIREMENTS |
| CORRESPONDING TO SIMSON CONNECTORS |
| SPECIFIED. THE DESIGN PROFESSIONAL |
| HASN,T GIVEN ANY VALUES FOR UPLIFT OR |
| OTHER VALUES OF RESISTANCE. NOR HAS THE |
| DESIGN PROFESSIONAL PROVIDED A ANCHOR |
| SCHEDULE INDICATING WHAT VALUES THAT |
| THEY PREFER TO USE.104.2.1 W.P.B. |
| ADMINISTRATIVE CODE DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 12) COMMENT #29A) FROM THE PREVIOUS |
| REVIEW. A-451 DETAIL #4, THE ATTACHMENT |
| OF THE FOAM BRAKET,PLANS DO NOT |
| PROVIDE WHAT TYPE OF ATTACHMENT METHOD |
| TO BE USED OR QUANITITY OF FASTENERS. |
| |
| 13) COMMENT #30 FROM THE PREVIOUS REVIEW |
| A442 DETAIL #8, THE BAHAMA SHUTTER IS TO |
| BE ATTACHED TO A 2X_, THE SHUTTER |
| PRODUCT APPROVAL PROVIDES FASTENERS FOR |
| THE SHUTTER BUT THE DETAIL LACKS HOW |
| THE FRAMING MEMBER IS ATTACHED TO THE |
| STRUCTURE. FASTENER, SIZE & SPACING. |
| |
| 14) COMMENT #32 FROM THE PEVIOUS REVIEW, |
| PROVIDE UNITITY OF TITLE FOR LOTS: |
| 74-43-43-09-01-000-0110 |
| 74-43-43-09-01-000-0090 |
| |
| 15) COMMENT #31 FROM THE PEVIOUS REVIEW, |
| BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| THESE COMMENTS MAY OR MAY NOT PERTAIN TO |
| BUILDING #1 SINCE THE PLANS HAVE ALL |
| BUILDINGS COMBINED, OTHER COMMENTS MAY |
| APPEAR THAT WERE NOT PART OF THE |
| PREVIOUS REVIEW SINCE ALL BUILDINGS ARE |
| INCORPORATED INTO ONE PLAN. PLEASE BREAK |
| THE MEP INTO A SINGLE UNIT, PLANS ARE TO |
| CUMBERSOME TO REVIEW AS IS, |
| |
| *********NOTE*******NOT ALL ROLLS OF |
| PLANS ARE COMPLETE,SOME ARE MISSING |
| THE STRUCTURAL PAGES TOTALLY. |
| |
| *********NOTE******PRODUCT APPROVALS (3) |
| SETS OF PRODUCT APPROVALS WILL BE |
| REQUIRED FOR PROJECT. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |