Plan Review Notes
Plan Review Notes For Permit 04110183
Permit Number 04110183
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110183
 ADD: 3900 N FLAGLER**BLDG# 1**
 CONT: MANHATTEN CONSTRUCTION
 TEL: (813)927-0209
 CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR
 OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL
 DESIGN
 OR METHODS OF CONSTRUCTION
  
 3)THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE. SITE IS LOCATED
 IN A (A5) FLOOD ZONE, THE MINIMUM
 FINISH
 SLAB MUST BE 7.5' NGVD.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) PLANS INDICATE THE USE OF AUGER
 PILE,
 THE SOILS ENGINEER TO PROVIDE
 INFORMATION AS TO WHAT THEY WIL BE
 INSPECTING, GROUT, SPACING DEPTH ETC
 SEE
 REQUIREMENTS IN SECTION 1809.2 FOR
 AUGERED PILE.
  
 6) PLANS ARE CUMBERSOME, OR UNWIELDY
 TRYING TO REVIEW 6 BUILDINGS IN ONE SET
 OF PLANS. WITH THE NUMBER OF PAGES AND
 DETAILS IT IS DIFFICULT TO TURN TOO,
 LOCATE AND REFRENCE THE VARIOUS
 DETAILS.
 THIS MAY CREATE ADDITIONALCOMMENTS
 THAT AREN'T ADDRESSED ON THE FIRST
 REVIEW, AT BEST BREAK OUT THE VARIOUS
 TRADES UNTIL A PERMIT SET OF PLANS IS
 APPROVED AND READY FOR PERMIT.
  
 7) A202 LIST VARIOUS DOORS AS EITHER
 "B" OR "C" LABELED DOORS, SEE TABLE
 705.1.2 THAT LIST THE DOOR RATING IN
 EITHER MINUTES OR HOURS.
  
 8) TRASH CHUTE- S8-4 DETAILS AA & BB
 BOTH HAVE THE @ HR RATED SHAFT STOPPING
 SHORT OF THE PLYWOOD ROOF SHEATHING.SEE
 705.2.3.4.2.
  
 9) F101 TYPICAL FLOORS 2-4 ARE MISSING
 THE FIRE SPRINKLER AT THE TOPAND
 ALTERNATING FLOORS LEVELS AND
 TERMINATION ROOM. 705.2.4.6
  
 10) S8-6, A442 & A464 VARIOUS DETAILS
 INDICATE THE USE OF 5/8" EXTERIOR
 SHEATHING? NO MENTION AS TO MATERIAL,
 TYPE V BUILDING.
  
 11) A.442 VARIOUS DETAILS INDICATE THE
 USE OF 6" METAL STUDS FOR EXTERIOIR
 FRAMING. WITHOUT THE WALL ASSEMBLY
 DESCRIPTION ABOVE UNABLE TO DETERMINE
 TABLE 2213.1A./ 2213.1B.
  
 12)FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 13) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, A106
 THE ELEVATOR LOBBY DOORS ARE NOT
 NUMBERED NOR THE FRONT ENTRY DOORS TO
 THE UNIT DO NOT HAVE FIRE RATINGS SEE
 TABLE 705.1.2.
  
 14) A.501 DETAILS INDICATE A 1/2"
 HANDRAIL SEE 1007.5.3.
  
 15) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, A502
 INDICATES A DETAIL OF THE ELEVATOR
 SHAFT
 3003.1.8 A METAL OR CONCRETE FLOOR
 SHALL
 BE PROVIDED AT THE TOP OF ALL
 HOISTWAYS.
 INDICATECODE COMPLIANCE, IF SO THEN
 PROVIDE THE DETAIL FOR THE 2 HR RATED
 CEILING.
  
 16) A502 INDICATES THE ELEVATOR VENTING
 BUT SIZE IS NOT GIVEN PROVIDE:
 3003.6.3 THE AREA OF THE VENTS SHALL
 BE
 NOT LESS THAN 3 SQ FT FOR EACH ELEVATOR
 CAR, WHICHEVER IS GREATER.
  
 17) A502 PROVIDE REPORT FOR THE 2HR
 RATED ACCESS HATCH.
  
 18) A503 INDICATES THE USE OF WOOD
 TRUSSES BUT NO INFORMATION PROVIDE FOR
 SOFFIT ATTIC VENTING? 2309.7.
  
 19) 301.13.1 GROUND MOUNTED A/C UNITS:
 GROUND-MOUNTED UNITS FOR R3 RESIDENTIAL
 APPLICATIONS MAY BE ANCHORED WITH # 14
 SCREWS WITH GASKETED WASHERS ACCORDING
 TO THE FOLLOWING:
 1) FOR UNITS WITH SIDES LESS THAN 12",
 ONE SCREW SHALL BE USED AT EACH SIDE OF
 THE UNIT.
 2) FOR UNITS BETWEEN 12" & 24", TWO
 SCREWS SHALL BE USED PER DIDE.
 3) FOR UNITS BETWEEN 24" & 36", THREE
 SCREWS SHALL BE USED PER SIDE.
 4) FOR UNITS GREATER THAN 36" OR 5
 TONS
 ANCHORAGE SHALL BE DESIGN IN ACCORDANCE
 WITH 301.13. (140 MPH).
  
 20)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERTABLE
 B)DOORS, SWING, SLIDING AND OVERHEAD
 C) MULLIONS
 D)LOUVERS
 E) EXTERIOR RAILINGS
 F) STORM SHUTTERS
 G) TRUSS ANCHORS
 H) EXTERIOR RAILINGS
 I) ROOFING ASSEMBLIES/ FLAT & PITCHED
 ROOFS
 J)SOFFIT- POLYBEAD
  
 21)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 22) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE
 LOADS
 APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 23)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE
 SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE
 THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 24) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 25)1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS
 THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE
 ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 26) MEAN ROOF HEIGHT IS ABOVE 35' THE
 WEST PALM NAILING AMENDMENTS ARE GOOD
 TO
 A ROOF HEIGHT OF 35'.
 ENGINEER TO PROVIDE THE ADDITIONAL
 NAILING FOR THE ROOF ZONES 1,2&3.
  
 TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
 PROVIDE THE NAILING REQUIREMENTS FOR
 ZONES 1,2&3 FOR ROOF AREAS OVER 35'.
  
 27) THE STRUCTURAL PLANS DO NOT PROVIDE
 A ROOF FRAMING PLAN WITH THE TRUSSES
 IDENTIFIED, NOR THE LOADS IDENTIFIED,
 UPLIFT, GRAVITY NOR F1,F2. THE ROOF
 TRUSSES ARE PART OF THE MAIN FORCE
 RESISTING SYSTEM AND SO ALL ELEMENTS OF
 THE TRUSS PACKAGE SYSTEM NEED TO BE
 ENGINEERED. SEE 1606.2.4.
  
 28) THERE IS NO TRUSS ANCHOR SCHEDULE
 IDENTIFYING THE MANUFACTURER MODEL
 NUMBER OF ANCHOR OR VALUE THE TRUSS
 ANCHOR CAN BE LOADED TO. SEE
 28A)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE
 TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD
 CARRY-
 ING CAPACITY.
  
 28B)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD
 LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS
 OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE
 EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE
 LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS
 SPE
 CIFIED IN THE MATERIALS SECTIONS OF
 THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 28C) THE COMMENT ON S9-1 "SEE LATEST
 SIMSON CATALOG FOR FASTENER
 REQUIREMENTS
 CORRESPONDING TO SIMSON CONNECTOR
 SPECIFIED. PLEASE EXPLAIN COMMENT.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL
 TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 29) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-451 DETAIL 4 PROVIDE THE FOLLOWING:
 A) ATTACHMENT OF THE FOAM BRAKET
 B) ATTACHMENT OF THE RIGID INSULATION
  
 BOARD
 C) 5/8 GYPSUM SOFFIT BOARD: ADDITIONAL
  
 INFORMATION ON PRODUCT?
  
 30) A442 DETAIL# 8 WINDOW HEADER W/
 BAHAMA SHUTTER PROVIDE ADDITIONAL
 INFORMATION, THE FASTENERS ARE LOCATED
 WITHIN 3/4" OF THE CONCRETE FACE, WILL
 THERE BE A REDUCTION IN LOADING FOR
 THIS
 FASTENING SYSTEM?
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 32) PROVIDE A UNITY OF TITLE FOR LOTS:
 74-43-43-09-01-000-0110
 74-43-43-09-01-000-0090
 TABLE 600 ISSUES MAY ARISE OTHERWISE.
  
 33) TABLE 500 ISSUES, TYPE "V"
 UNPROTECTED ONLY ALLOWS 2 STORIES, TO
 CLAIM THE HEIGHT OF A (4) STORY BUILDING
 TABLE 500 FOOTNOTE "J" AND 903.2 WILL
 REQUIRE A FULL NFPA 13 FIRE SPRINKLER
 SYSTEM. THE ONLY EXCEPTION IS 503.2.2
 FOR TYPE I, II
 OR TYPEIII.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026