2004-12-08 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04110183 |
| ADD: 3900 N FLAGLER**BLDG# 1** |
| CONT: MANHATTEN CONSTRUCTION |
| TEL: (813)927-0209 |
| CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, DIRECTOR |
| OF |
| THE RESIDENT INSPECTOR PROGRAM.A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| ON THIS PROJECT, DUE TO ONE OR MORE OF |
| THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL |
| DESIGN |
| OR METHODS OF CONSTRUCTION |
| |
| 3)THE FINISHED FLOOR LEVEL SHALL BE |
| VERIFIED BY A SIGNED AND SEALED |
| ELEVATION CERTIFICATE. SITE IS LOCATED |
| IN A (A5) FLOOD ZONE, THE MINIMUM |
| FINISH |
| SLAB MUST BE 7.5' NGVD. |
| |
| 4) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN |
| QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE |
| EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| |
| 5) PLANS INDICATE THE USE OF AUGER |
| PILE, |
| THE SOILS ENGINEER TO PROVIDE |
| INFORMATION AS TO WHAT THEY WIL BE |
| INSPECTING, GROUT, SPACING DEPTH ETC |
| SEE |
| REQUIREMENTS IN SECTION 1809.2 FOR |
| AUGERED PILE. |
| |
| 6) PLANS ARE CUMBERSOME, OR UNWIELDY |
| TRYING TO REVIEW 6 BUILDINGS IN ONE SET |
| OF PLANS. WITH THE NUMBER OF PAGES AND |
| DETAILS IT IS DIFFICULT TO TURN TOO, |
| LOCATE AND REFRENCE THE VARIOUS |
| DETAILS. |
| THIS MAY CREATE ADDITIONALCOMMENTS |
| THAT AREN'T ADDRESSED ON THE FIRST |
| REVIEW, AT BEST BREAK OUT THE VARIOUS |
| TRADES UNTIL A PERMIT SET OF PLANS IS |
| APPROVED AND READY FOR PERMIT. |
| |
| 7) A202 LIST VARIOUS DOORS AS EITHER |
| "B" OR "C" LABELED DOORS, SEE TABLE |
| 705.1.2 THAT LIST THE DOOR RATING IN |
| EITHER MINUTES OR HOURS. |
| |
| 8) TRASH CHUTE- S8-4 DETAILS AA & BB |
| BOTH HAVE THE @ HR RATED SHAFT STOPPING |
| SHORT OF THE PLYWOOD ROOF SHEATHING.SEE |
| 705.2.3.4.2. |
| |
| 9) F101 TYPICAL FLOORS 2-4 ARE MISSING |
| THE FIRE SPRINKLER AT THE TOPAND |
| ALTERNATING FLOORS LEVELS AND |
| TERMINATION ROOM. 705.2.4.6 |
| |
| 10) S8-6, A442 & A464 VARIOUS DETAILS |
| INDICATE THE USE OF 5/8" EXTERIOR |
| SHEATHING? NO MENTION AS TO MATERIAL, |
| TYPE V BUILDING. |
| |
| 11) A.442 VARIOUS DETAILS INDICATE THE |
| USE OF 6" METAL STUDS FOR EXTERIOIR |
| FRAMING. WITHOUT THE WALL ASSEMBLY |
| DESCRIPTION ABOVE UNABLE TO DETERMINE |
| TABLE 2213.1A./ 2213.1B. |
| |
| 12)FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| PROVIDE ENERGY CALS/ W MANUAL "J" |
| |
| 13) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, A106 |
| THE ELEVATOR LOBBY DOORS ARE NOT |
| NUMBERED NOR THE FRONT ENTRY DOORS TO |
| THE UNIT DO NOT HAVE FIRE RATINGS SEE |
| TABLE 705.1.2. |
| |
| 14) A.501 DETAILS INDICATE A 1/2" |
| HANDRAIL SEE 1007.5.3. |
| |
| 15) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, A502 |
| INDICATES A DETAIL OF THE ELEVATOR |
| SHAFT |
| 3003.1.8 A METAL OR CONCRETE FLOOR |
| SHALL |
| BE PROVIDED AT THE TOP OF ALL |
| HOISTWAYS. |
| INDICATECODE COMPLIANCE, IF SO THEN |
| PROVIDE THE DETAIL FOR THE 2 HR RATED |
| CEILING. |
| |
| 16) A502 INDICATES THE ELEVATOR VENTING |
| BUT SIZE IS NOT GIVEN PROVIDE: |
| 3003.6.3 THE AREA OF THE VENTS SHALL |
| BE |
| NOT LESS THAN 3 SQ FT FOR EACH ELEVATOR |
| CAR, WHICHEVER IS GREATER. |
| |
| 17) A502 PROVIDE REPORT FOR THE 2HR |
| RATED ACCESS HATCH. |
| |
| 18) A503 INDICATES THE USE OF WOOD |
| TRUSSES BUT NO INFORMATION PROVIDE FOR |
| SOFFIT ATTIC VENTING? 2309.7. |
| |
| 19) 301.13.1 GROUND MOUNTED A/C UNITS: |
| GROUND-MOUNTED UNITS FOR R3 RESIDENTIAL |
| APPLICATIONS MAY BE ANCHORED WITH # 14 |
| SCREWS WITH GASKETED WASHERS ACCORDING |
| TO THE FOLLOWING: |
| 1) FOR UNITS WITH SIDES LESS THAN 12", |
| ONE SCREW SHALL BE USED AT EACH SIDE OF |
| THE UNIT. |
| 2) FOR UNITS BETWEEN 12" & 24", TWO |
| SCREWS SHALL BE USED PER DIDE. |
| 3) FOR UNITS BETWEEN 24" & 36", THREE |
| SCREWS SHALL BE USED PER SIDE. |
| 4) FOR UNITS GREATER THAN 36" OR 5 |
| TONS |
| ANCHORAGE SHALL BE DESIGN IN ACCORDANCE |
| WITH 301.13. (140 MPH). |
| |
| 20)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR |
| PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 |
| FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED & OPERTABLE |
| B)DOORS, SWING, SLIDING AND OVERHEAD |
| C) MULLIONS |
| D)LOUVERS |
| E) EXTERIOR RAILINGS |
| F) STORM SHUTTERS |
| G) TRUSS ANCHORS |
| H) EXTERIOR RAILINGS |
| I) ROOFING ASSEMBLIES/ FLAT & PITCHED |
| ROOFS |
| J)SOFFIT- POLYBEAD |
| |
| 21)1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN |
| INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 22) 1707.4.5.2 MULLIONS SHALL BE |
| DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE |
| LOADS |
| APPLIED BY THE WINDOW OR DOOR |
| ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 23)1503.4.2 OVERFLOW DRAINS SHALL BE |
| THE |
| SAME SIZE AS ROOF DRAINS, INSTALLED |
| WITH |
| THE INLET FLOW LINE LOCATED 2" ABOVE |
| THE |
| LOWEST POINT OF THE ROOF LINE. OVERFLOW |
| SCUPPERS SHALL BE A MINIMUM OF 4"IN |
| HEIGTH AND SHALL BE PLACED IN WALLS OR |
| PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF |
| SURFACE. |
| |
| 24) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 25)1511.7 ROOF MOUNTED MECHANICAL UNITS |
| SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| MECH. 301.13 WIND RESISTANCE MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUP PORTS |
| THAT |
| ARE EXPOSED TO WIND SHALL BE DESIGNED |
| AND INSTALLED TO RESIST THE WIND |
| PRESSURES ON THE EQUIPMENT & THE |
| SUPPORTS AS DETERMINED IN ACCORDANCE |
| WITH THE FL BLD CODE. THIS MAY BE |
| ACCOMP |
| LISHED BY DESIGN OR BY APPLICATION OF |
| SECTION 301.13.1. |
| |
| 26) MEAN ROOF HEIGHT IS ABOVE 35' THE |
| WEST PALM NAILING AMENDMENTS ARE GOOD |
| TO |
| A ROOF HEIGHT OF 35'. |
| ENGINEER TO PROVIDE THE ADDITIONAL |
| NAILING FOR THE ROOF ZONES 1,2&3. |
| |
| TABLE 2306.1 PALM BEACH COUNTY |
| AMENDMENTS |
| ROOF SHEATHING NAILING REQUIREMENTS |
| |
| ZONE 1 & 28D COMMON |
| 6" EDGES & 6" INTERMEDIATES |
| |
| ZONE 38DCOMMON |
| 4" EDGES & 6" INTERMEDIATES |
| PROVIDE THE NAILING REQUIREMENTS FOR |
| ZONES 1,2&3 FOR ROOF AREAS OVER 35'. |
| |
| 27) THE STRUCTURAL PLANS DO NOT PROVIDE |
| A ROOF FRAMING PLAN WITH THE TRUSSES |
| IDENTIFIED, NOR THE LOADS IDENTIFIED, |
| UPLIFT, GRAVITY NOR F1,F2. THE ROOF |
| TRUSSES ARE PART OF THE MAIN FORCE |
| RESISTING SYSTEM AND SO ALL ELEMENTS OF |
| THE TRUSS PACKAGE SYSTEM NEED TO BE |
| ENGINEERED. SEE 1606.2.4. |
| |
| 28) THERE IS NO TRUSS ANCHOR SCHEDULE |
| IDENTIFYING THE MANUFACTURER MODEL |
| NUMBER OF ANCHOR OR VALUE THE TRUSS |
| ANCHOR CAN BE LOADED TO. SEE |
| 28A)1707.3.1 JOIST HANGERS, FRAMING |
| ANCHORS & SIMILAR DEVICES SHALL BE |
| TEST- |
| ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| LABELED AND LISTED FOR THEIR LOAD |
| CARRY- |
| ING CAPACITY. |
| |
| 28B)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD |
| LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS |
| OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE |
| EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE |
| LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS |
| SPE |
| CIFIED IN THE MATERIALS SECTIONS OF |
| THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| 28C) THE COMMENT ON S9-1 "SEE LATEST |
| SIMSON CATALOG FOR FASTENER |
| REQUIREMENTS |
| CORRESPONDING TO SIMSON CONNECTOR |
| SPECIFIED. PLEASE EXPLAIN COMMENT. |
| 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL |
| TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND |
| THE TECHNICAL CODES "SHALL NOT BE CITED |
| AS A WHOLE OR IN PART, NOR THE TERM |
| "LEGAL" OR ITS RQUIVALENT BE USED AS A |
| SUBSTITUTE FOR SPECIFIC INFORMATION". |
| |
| 29) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| A-451 DETAIL 4 PROVIDE THE FOLLOWING: |
| A) ATTACHMENT OF THE FOAM BRAKET |
| B) ATTACHMENT OF THE RIGID INSULATION |
| |
| BOARD |
| C) 5/8 GYPSUM SOFFIT BOARD: ADDITIONAL |
| |
| INFORMATION ON PRODUCT? |
| |
| 30) A442 DETAIL# 8 WINDOW HEADER W/ |
| BAHAMA SHUTTER PROVIDE ADDITIONAL |
| INFORMATION, THE FASTENERS ARE LOCATED |
| WITHIN 3/4" OF THE CONCRETE FACE, WILL |
| THERE BE A REDUCTION IN LOADING FOR |
| THIS |
| FASTENING SYSTEM? |
| |
| 31) BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE |
| ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 32) PROVIDE A UNITY OF TITLE FOR LOTS: |
| 74-43-43-09-01-000-0110 |
| 74-43-43-09-01-000-0090 |
| TABLE 600 ISSUES MAY ARISE OTHERWISE. |
| |
| 33) TABLE 500 ISSUES, TYPE "V" |
| UNPROTECTED ONLY ALLOWS 2 STORIES, TO |
| CLAIM THE HEIGHT OF A (4) STORY BUILDING |
| TABLE 500 FOOTNOTE "J" AND 903.2 WILL |
| REQUIRE A FULL NFPA 13 FIRE SPRINKLER |
| SYSTEM. THE ONLY EXCEPTION IS 503.2.2 |
| FOR TYPE I, II |
| OR TYPEIII. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT |
| NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR |
| SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |