Plan Review Notes For Permit 04110145
Permit Number 04110145
Review Stop B
Sequence Number 3
Notes
Date Text
2005-12-02 00:00:00DENIED
  
  
  
  
 1) PERMIT CANNOT BE RESTAMPED WHEN IT
 DOES NOT MATCH THE INFORMATION ON FILE,
 IT MUST BE A REVISION. THE FOLLOWING
 INFORMATION HAS CHANGED.
  
 1A) CONTRACTOR IS NOT THE SAME, SUBMIT A
 LETTER ON OLD CONTRACTORS LETTERHEAD
 THAT THEY ARE RELEASING THE JOB,PERMIT,
 FEES,ETC. TO THE NEW CONTRACTOR.
  
 1B) ENGINEERED BEAM SIZES AND SPANS WERE
 CHANGED. A NEW REVISION MUST BE
 SUBMITTED THAT WILL MEET THE NEW PBC
 POST 2004 HURRICANE SEASON UPDATED
 ENGINEERING SPECIFICATIONS
  
 1C) A NOTICE OF COMMENCEMENT WAS NOT
 SUMITTED. THIS MUST BE SUPPLIED BEFORE
 A REVISED PEMIT CAN BE ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716