2004-11-12 00:00:00 | ********** UNSAT **************** | | | | 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | /LOAD CALCULATIONS WITH ALL EQUIPMENT | | SHOWN ON ELECTRICAL RISER DIAGRAM FOR | | POOL EQUIPMENT. | | BLOWER SHOWN AS OPTIONAL? | | | | 2)NOTE: PLEASE SEE ALL CONTINUOUS LOADS | | ARE TO BE SHOWN AT 125%/ PUMP/ | | HEAT-PUMP. 215.3,230.42 ETC. | | PLEASE SEE LOAD IS SHOWN MAXED AT 70A'S | | ALREADY. | | PLEASE ALSO INCLUDE LOAD CALCULATIONS | | FOR EXISTING SERVICE INCLUDING NEW | | LOADS | | BEING ADDED.220.31B | | | | 3)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | REQUIRES THE PRINTED NAME AND SIGNATURE | | OF PERSON RESPONSIBLE FOR PLANS. | | | | THE ABOVE NOTES ARE NOT FOR THE PLANS | | SUBMITTED DONE BY ENGINEER. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | ONLY INSERT NEW SHEETS INTO COMPLETE | | SETS FOR REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|