Date |
Text |
2004-11-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHTS A-1, A-2, & P-1 (A) INDICATES |
| "3/4 INCH GALV. GAS PIPE & 1/2 INCH |
| WATER AT THESE LOCATIONS ON SHTS A-1 & |
| A-2, BUT SHT P-1 INDICATES THAT THE (A) |
| LOCATIONS ARE FOR WASTE AND VENT LINE |
| PLUS COLD WATER. PLEASE CORRELATE |
| PUMBING SHEETS WITH THE ARCHITECTURAL |
| SHEETS. SECTION 104.2.1 |
| 2) A PROFESSIONAL ENGINEER SHALL SIGN |
| HES NAME. INITIALS ARE NOT APPROVED. |
| FAC |
| 61G15-23.002(1) & FS 471.025 |
| 3 THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE GAS PERMIT REQUIRED. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. - SHOW THE EXISTING |
| SYSTEM AND ALL PIPE SIZES, WITH |
| EXISTING |
| BTU LOAD ON THE SYSTEM. |
| B. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34).- THE TOTAL BTU LOAD FOR THE |
| EXISTING SYSTEM SHALL BE SHOWN AS WELL |
| AT THE TOTAL BTU LOAD FOR NEW SYSTEM. |
| C. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM |
| PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| D) SHT P-2 SHOWS 13 GAS OUTLETS AT 1200 |
| BTU PER OUTLET. THIS ADDS UP TO 15,600 |
| BUT'S, BUT GAS INFORMATION INDICATES |
| THAT IT IS 20,400 BTU'S PLEASE CLARIFY. |
| SECTION 104.2.1 |
| |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |