2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS A-1, A-2, & P-1 (A) INDICATES
 "3/4 INCH GALV. GAS PIPE & 1/2 INCH
 WATER AT THESE LOCATIONS ON SHTS A-1 &
 A-2, BUT SHT P-1 INDICATES THAT THE (A)
 LOCATIONS ARE FOR WASTE AND VENT LINE
 PLUS COLD WATER. PLEASE CORRELATE
 PUMBING SHEETS WITH THE ARCHITECTURAL
 SHEETS. SECTION 104.2.1
 2) A PROFESSIONAL ENGINEER SHALL SIGN
 HES NAME. INITIALS ARE NOT APPROVED.
 FAC
 61G15-23.002(1) & FS 471.025
 3 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - SHOW THE EXISTING
 SYSTEM AND ALL PIPE SIZES, WITH
 EXISTING
 BTU LOAD ON THE SYSTEM.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).- THE TOTAL BTU LOAD FOR THE
 EXISTING SYSTEM SHALL BE SHOWN AS WELL
 AT THE TOTAL BTU LOAD FOR NEW SYSTEM.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM
 PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D) SHT P-2 SHOWS 13 GAS OUTLETS AT 1200
 BTU PER OUTLET. THIS ADDS UP TO 15,600
 BUT'S, BUT GAS INFORMATION INDICATES
 THAT IT IS 20,400 BTU'S PLEASE CLARIFY.
 SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]