Plan Review Notes
Plan Review Notes For Permit 04101262
Permit Number 04101262
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECTURAL SHEETS: PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT IS
 REQUIRED PER FAC 61G1-16.004(6) AND FS
 481.2055.
 2) SHOW CLEAR FLOOR SPACE FOR LAVS,
 WATER CLOSETS, AND URINAL PER SECTIONS
 11-4.16.2, 11-4.18.3, 11-4.19.3, AND
 11-4.22.3.
 3) SUBMIT A DETAIL FOR THE PANTRY SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 4) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1
 5) SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN FOR PIPING. THE SINK SHALL
 NOT DRAIN THROUGH THE HORIZONTEL WET
 VENT OF THE TOILET ROOMS. SECTION 909.1.
 THE SINK SHALL CONNECT DOWNSTREAM OF THE
 WET-VENTED FIXTURES. (SEE RED LINE
 EXAMPLE ON ONE SET OF PLANS.
 6) SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. SECTION
 604.9
 IF WATER HAMMER ARRESTORS ARE INSTALLED,
 THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 210 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]