Date |
Text |
2004-11-27 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) ARCHITECTURAL SHEETS: PRINTED NAME OF |
| THE PERSON SEALING THE DOCUMENT IS |
| REQUIRED PER FAC 61G1-16.004(6) AND FS |
| 481.2055. |
| 2) SHOW CLEAR FLOOR SPACE FOR LAVS, |
| WATER CLOSETS, AND URINAL PER SECTIONS |
| 11-4.16.2, 11-4.18.3, 11-4.19.3, AND |
| 11-4.22.3. |
| 3) SUBMIT A DETAIL FOR THE PANTRY SINK |
| SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| AND ALL SUBSECTIONS. |
| 4) A DRINKING FOUNTAIN IS REQUIRED PER |
| TABLE 403.1. ALSO SEE SECTION 410.1 |
| 5) SHT P-1 SANITARY RISER DIAGRAM AND |
| FLOOR PLAN FOR PIPING. THE SINK SHALL |
| NOT DRAIN THROUGH THE HORIZONTEL WET |
| VENT OF THE TOILET ROOMS. SECTION 909.1. |
| THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| WET-VENTED FIXTURES. (SEE RED LINE |
| EXAMPLE ON ONE SET OF PLANS. |
| 6) SHT P-1 WATER RISER DIAGRAM, AIR |
| CHAMBERS ARE NOT APPROVED. SECTION |
| 604.9 |
| IF WATER HAMMER ARRESTORS ARE INSTALLED, |
| THEY SHALL BE LOCATED NEAR THE FIXTURE |
| IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING. PDI-WH 210 AND MANUF. |
| INSTALLATION INSTRUCTIONS. |
| |
| REVIEW BY KEN STEVENS |