Plan Review Notes For Permit 04101262 |
Permit Number |
04101262 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-11-05 00:00:00 | DENIED | | | | | | 1.DOORS IN HALLWAY AT BATHROOMS AND | | HVAC CLOSET SHALL COMPLY WITH THE | | FOLLOWING. | | 1012.1.4. DURING ITS SWING, ANY | | DOOR IN A MEANS OF EGRESS SHALL LEAVE | | UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE | | REQUIRED WIDTH OF AN AISLE, CORRIDOR, | | PASSAGEWAY, OR LANDING, NOR PROJECT MORE | | THAN 7" INTO THE REQUIRED WIDTH. | | | | 2.PANTRY SINK HEIGHT SHALL COMPLY WITH | | | | FBC 11-4.24.2 ALSO KNEE CLEARANCE SHALL | | COMPLY WITH FBC 11-4.24.3 | | SHOW DETAIL ON PLANS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | BUILDING PLAN REVIEW | | ART LANGE | | TEL: (561)805-6672 | | FAX: (561)659-8026 |
|