Plan Review Notes
Plan Review Notes For Permit 04101222
Permit Number 04101222
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-11-15 00:00:00DENIED
  
 1) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR
 TO FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 2) WEST PALM BEACH FIRE MARSHAL OFFICE
 REQUIRES DUCT DETECTORS TO SEND A
 "ALARM" CONDITION, NOT A "SUPERVISORY".
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722