Plan Review Notes
Plan Review Notes For Permit 04101165
Permit Number 04101165
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00******** PROVISO/REVISION ********
  
 1)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52, 210.52E
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE IS
 MISSING HEAT PUMP AS SHOWN ON PLANS AND
 LOAD CALCULATIONS.
 215.5
  
 3)NOTE: PLEASE INDICATE GARAGE RECETPS
 AS GFI/GFI PROTECTED. 210.8
  
 4 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH ANY OTHER POSSISBLE
 REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.
 IF PLANS COME BACK FOR ANY OTHER
 CORRECTIONS BEFORE PERMIT IS ISSUED,
 THIS MAY BE DONE AT THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.