Date |
Text |
2005-01-26 00:00:00 | 1. DOORS 132 FOR MECHANICAL ROOM 132 |
| ARE NOT FIRE RATED BUT ARE LOCATED |
| IN A RATED WALL. PLEASE REVISE PLANS |
| TO REFLECT THAT THESE DOORS WILL BE |
| FIRE RATED. |
| |
| 2. ALL FIRE RATED DOORS ARE TO BE |
| EQUIPPED WITH LISTED AND APPROVED |
| SELF-CLOSING DEVICES TO CAUSE THE |
| DOORS TO POSITIVELY LATCH WHEN |
| CLOSED. |
| |
| 3. SINCE THE BUILDING IS NEW, THE |
| FIRE ALARM SYSTEM MUST BE MONITORED |
| BY UL LISTED CENTRAL STATION APPROVED |
| FOR CENTRAL STATION SERVICE. YOUR |
| RESPONSE TO COMMENT # 19 IS NOT |
| CORRECT AS THE EXISTING BUILDINGS |
| THAT ARE PRESENTLY MONITORED ON THE |
| CAMPUS DID NOT HAVE TO MEET THIS |
| SPECIFIC REQUIREMENTS. PLEASE NOTE |
| THIS. |
| |
| 4. PLEASE EXPLAIN TYPICAL CARD READER |
| OUTLETS ON PAGE E1.9. HOW WILL CARD |
| READERS BE USED AND WILL THEY POSE |
| ANY PROBLEMS FOR EXITING. |
| |
| 5. MAG-LOCKS APPEAR TO BE NOTED ON |
| DOORS MARKED AS EXITS BETWEEN ROOM 140 |
| AND 142. PLEASE EXPLAIN USE OF LOCKS |
| AND EXITING. |
| |
| 6. FIRE SPRINKLER PROTECTION WILL |
| BE REQUIRED UNDERNEATH DUCTS THAT ARE |
| OVER FOUR FEET WIDE. |
| |
| 7. THE STORAGE OF BASKETBALLS AND |
| SHELVING CANNOT DAMAGE OR INTERFERE |
| WITH THE FIRE ALARM EQUIPMENT |
| LOCATED AT RECEPTION AREA. |
| |
| 8. IT APPEARS THAT ONLY SEVEN FIRE |
| EXTINGUISHERS ARE PRESENT WITH ONE |
| BEING LOCKED IN MECHANICAL ROOM # 166. |
| ADDITIONAL FIRE EXTINGUISHERS APPEAR |
| TO BE NEEDED. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |