Plan Review Notes
Plan Review Notes For Permit 04100894
Permit Number 04100894
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100894
 ADD: 2600 NORTH MILITARY TRAIL
 CONT: THE WEITZ CO
 TEL: (561)723-5976
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 2ND SESSION STARTING COMMENT# 26
 ACTION: FAILED
  
  
 26) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 27) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPARATABLE
 B) WINDOWS GLASS BLOCK
 C) MULLIONS
 D) DOORS, EXTERIOR W/ GLAZING
 E) DOORS, EXTERIOR SOLID
 F) LOUVERS
 G) COMPONENTS & CLADDING
 (1) CEMENT BOARD- SUBSHEATHING
 H) ROOFING ASSEMBLIES
 (1) INSULATION
 (2) ROOFING PRODUCTS
  
 28)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND
 TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 29) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 30) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE
 LOADS
 APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 31) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 32) PROVIDE FLAMESPREAD AND SMOKE
 DEVELOPMENT INFORMATION ON THE GYM
 DIVIDING CURTAIN, TABLE 803.3.
  
 33) PLEASE INDICATE EXITING (LIFE SAFETY
 PLAN) INDICATING OCCUPANT LOADS FOR
 ROOMS AND EXITING REQUIREMENTS SEE
 TABLE 1003.1. & TABLE 1004 FOR EXITS AND
 MEANS OF EGRESS.
  
 34) A7.3 MEZZANINE DETAIL INDICATES THE
 USE OF A STEEL LADDEER VS STAIRS SEE
 1005.7.3 EGRESS STAIRWAYS FROM
 MEZAANINES SHALL CONFORM WITH THE
 REQUIREMENTS OF 1007 ALSO SEE EXCEPTION
 AND REQUIRED SMOKE DETECTION SYSTEM AND
 FIRE ALARM.
  
 35) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026