2004-11-29 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04100894 |
| ADD: 2600 NORTH MILITARY TRAIL |
| CONT: THE WEITZ CO |
| TEL: (561)723-5976 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| 2ND SESSION STARTING COMMENT# 26 |
| ACTION: FAILED |
| |
| |
| 26) 1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR |
| PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 |
| FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| |
| 27) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED & OPARATABLE |
| B) WINDOWS GLASS BLOCK |
| C) MULLIONS |
| D) DOORS, EXTERIOR W/ GLAZING |
| E) DOORS, EXTERIOR SOLID |
| F) LOUVERS |
| G) COMPONENTS & CLADDING |
| (1) CEMENT BOARD- SUBSHEATHING |
| H) ROOFING ASSEMBLIES |
| (1) INSULATION |
| (2) ROOFING PRODUCTS |
| |
| 28)1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND |
| TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| 29) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 30) 1707.4.5.2 MULLIONS SHALL BE |
| DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE |
| LOADS |
| APPLIED BY THE WINDOW OR DOOR |
| ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 31) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY. |
| |
| 32) PROVIDE FLAMESPREAD AND SMOKE |
| DEVELOPMENT INFORMATION ON THE GYM |
| DIVIDING CURTAIN, TABLE 803.3. |
| |
| 33) PLEASE INDICATE EXITING (LIFE SAFETY |
| PLAN) INDICATING OCCUPANT LOADS FOR |
| ROOMS AND EXITING REQUIREMENTS SEE |
| TABLE 1003.1. & TABLE 1004 FOR EXITS AND |
| MEANS OF EGRESS. |
| |
| 34) A7.3 MEZZANINE DETAIL INDICATES THE |
| USE OF A STEEL LADDEER VS STAIRS SEE |
| 1005.7.3 EGRESS STAIRWAYS FROM |
| MEZAANINES SHALL CONFORM WITH THE |
| REQUIREMENTS OF 1007 ALSO SEE EXCEPTION |
| AND REQUIRED SMOKE DETECTION SYSTEM AND |
| FIRE ALARM. |
| |
| 35) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |