2004-11-12 00:00:00 | 1) DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH |
| NFPA 241. |
| |
| 2) SUITABLE ROADS ARE REQUIRED FOR |
| FIRE AND PARAMEDICAL ACCESS WHILE |
| BUILDING IS UNDER CONSTRUCTION. |
| |
| 3) ELECTRONIC SWITCHES ARE |
| REQUIRED ON FIRE LINE BACKFLOW |
| DEVICE. |
| |
| 4) PLEASE ILLUSTRATE FIRE RESCUE |
| STAGING LOCATIONS FOR FIRE |
| APPARATUS. IT DOES NOT APPEAR THAT |
| MANY LOCATIONS HAVE BEEN PROVIDED |
| FOR FIRE RESCUE ACCESS. THE AREAS |
| SEEN WOULD BE DIFFICULT TO TURN |
| FIRE APPARATUS AROUND. |
| |
| 5) PLEASE INDICATE PROPOSED OCCUPANT |
| LOADS FOR THE PROPOSED BUILDING. |
| ALL ANCILLARY ROOMS TO THE GYM |
| SHALL BE CALCULATED. |
| |
| 6) PLEASE PROVIDE FLAMESPREAD DATA |
| ON GYMNASIUM DIVIDING CURTAIN. |
| |
| 7) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND |
| CEILINGS. |
| |
| 8) TACTILE SIGNAGE REQUIRED AT |
| ALL EXIT LOCATIONS. |
| |
| 9) SINCE THE BUILDING IS A MIXED |
| OCCUPANCY, THE MOST STRINGENT OF |
| THE OCCUPANCY TYPES WILL PREVAIL. |
| |
| 10) PLEASE EXPLAIN THE DESIGN TEAMS |
| THEORY FOR THE MAIN INGRESS AND EGRESS |
| FOR THE BUILDING. |
| |
| 11) MORE DETAILS REQUIRED ABOUT THE |
| BLEACHERS. |
| |
| 12) ALL AUTMATIC SLIDERS USED FOR |
| EXITING MUST MEET THE REQUIREMENTS FOR |
| POWER OPERATED DOORS AND CONTAIN THE |
| REQUIRED OPENING FEATURE WHEN LOSS |
| OF POWER OCCURS. |
| |
| 13) PLEASE EXPLAIN UNDERCUT NOTE 3/8" |
| FOR RATED FIRE DOORS. |
| |
| 14) PANIC HARDWARE OR FIRE EXIT |
| HARDWARE |
| FOR FIRE RATED DOORS SHALL BE PRESENT |
| ON EXIT DOORS SUBJECT TO AN OCCUPANCY |
| OF 100 OR MORE PERSONS. |
| |
| 15) FIRE SPRINKLER HEADS SHALL NOT |
| BE PAINTED WHEN CEILING AREAS ARE |
| PAINTED. ANY FIRE SPRINKLER HEADS |
| THAT ARE PAINTED SHALL BE REPLACED. |
| |
| 16) ANY SHAFT LARGE ENOUGH FOR PERSONS |
| TO FALL INTO MUST BE MARKED "SHAFTWAY" |
| WITH 6" HIGH LETTERS ON A CONTRASTING |
| BACKGROUND. |
| |
| 17) BUILDING ADDRESS REQUIRED. A |
| MINIMUM |
| OF AT LEAST 6" HIGH NUMBERS ARE |
| REQUIRED. |
| |
| 18) PLEASE PROVIDE FLAMESPREAD RATINGS |
| ON ACCOSTICAL PANELS. |
| |
| 19) FIRE ALARM SYSTEM SHALL BE |
| MONITORED |
| BY A UL LISTED FIRE ALARM COMPANY |
| LISTED |
| FOR CENTRAL STATION SERVICE. |
| |
| |
| 20) PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| AND GUARDRAILS. |
| |
| 21) PLEASE EXPLAIN STEEL ACCESS |
| LADDERS. |
| WHAT IS THE RATIONALE BEING USED. |
| |
| 22) ON PAGE A10.1 AN AREA IS LABELED |
| STORAGE 130 WHICH APPEARS TO BE |
| INCORRECT. |
| |
| 23) SOME EXIT SIGNS APPEAR TO BE |
| MISSING FROM SOME OF THE ELECTRICAL |
| PAGES. |
| |
| 24) WHAT PREVENTS EMERGENCY LIGHTING |
| AND EXIT SIGNS IN THE GYM FROM |
| BEING DAMAGED. |
| |
| 25) WHAT WILL THE VOICE EVACUATION |
| MESSAGE SAY FOR THE FIRE ALARM |
| SYSTEM. |
| |
| 26) A NEW FIRE HYDRANT APPEARS |
| TO BE LOCATED NEW THE NEW |
| TRANSFORMERS BUT COULD NOT |
| LOCATE A CALL-OUT FOR IT ON THE |
| PLANS. |
| |