2004-11-12 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 2) SUITABLE ROADS ARE REQUIRED FOR
 FIRE AND PARAMEDICAL ACCESS WHILE
 BUILDING IS UNDER CONSTRUCTION.
  
 3) ELECTRONIC SWITCHES ARE
 REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 4) PLEASE ILLUSTRATE FIRE RESCUE
 STAGING LOCATIONS FOR FIRE
 APPARATUS. IT DOES NOT APPEAR THAT
 MANY LOCATIONS HAVE BEEN PROVIDED
 FOR FIRE RESCUE ACCESS. THE AREAS
 SEEN WOULD BE DIFFICULT TO TURN
 FIRE APPARATUS AROUND.
  
 5) PLEASE INDICATE PROPOSED OCCUPANT
 LOADS FOR THE PROPOSED BUILDING.
 ALL ANCILLARY ROOMS TO THE GYM
 SHALL BE CALCULATED.
  
 6) PLEASE PROVIDE FLAMESPREAD DATA
 ON GYMNASIUM DIVIDING CURTAIN.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 8) TACTILE SIGNAGE REQUIRED AT
 ALL EXIT LOCATIONS.
  
 9) SINCE THE BUILDING IS A MIXED
 OCCUPANCY, THE MOST STRINGENT OF
 THE OCCUPANCY TYPES WILL PREVAIL.
  
 10) PLEASE EXPLAIN THE DESIGN TEAMS
 THEORY FOR THE MAIN INGRESS AND EGRESS
 FOR THE BUILDING.
  
 11) MORE DETAILS REQUIRED ABOUT THE
 BLEACHERS.
  
 12) ALL AUTMATIC SLIDERS USED FOR
 EXITING MUST MEET THE REQUIREMENTS FOR
 POWER OPERATED DOORS AND CONTAIN THE
 REQUIRED OPENING FEATURE WHEN LOSS
 OF POWER OCCURS.
  
 13) PLEASE EXPLAIN UNDERCUT NOTE 3/8"
 FOR RATED FIRE DOORS.
  
 14) PANIC HARDWARE OR FIRE EXIT
 HARDWARE
 FOR FIRE RATED DOORS SHALL BE PRESENT
 ON EXIT DOORS SUBJECT TO AN OCCUPANCY
 OF 100 OR MORE PERSONS.
  
 15) FIRE SPRINKLER HEADS SHALL NOT
 BE PAINTED WHEN CEILING AREAS ARE
 PAINTED. ANY FIRE SPRINKLER HEADS
 THAT ARE PAINTED SHALL BE REPLACED.
  
 16) ANY SHAFT LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED "SHAFTWAY"
 WITH 6" HIGH LETTERS ON A CONTRASTING
 BACKGROUND.
  
 17) BUILDING ADDRESS REQUIRED. A
 MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 18) PLEASE PROVIDE FLAMESPREAD RATINGS
 ON ACCOSTICAL PANELS.
  
 19) FIRE ALARM SYSTEM SHALL BE
 MONITORED
 BY A UL LISTED FIRE ALARM COMPANY
 LISTED
 FOR CENTRAL STATION SERVICE.
  
  
 20) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 21) PLEASE EXPLAIN STEEL ACCESS
 LADDERS.
 WHAT IS THE RATIONALE BEING USED.
  
 22) ON PAGE A10.1 AN AREA IS LABELED
 STORAGE 130 WHICH APPEARS TO BE
 INCORRECT.
  
 23) SOME EXIT SIGNS APPEAR TO BE
 MISSING FROM SOME OF THE ELECTRICAL
 PAGES.
  
 24) WHAT PREVENTS EMERGENCY LIGHTING
 AND EXIT SIGNS IN THE GYM FROM
 BEING DAMAGED.
  
 25) WHAT WILL THE VOICE EVACUATION
 MESSAGE SAY FOR THE FIRE ALARM
 SYSTEM.
  
 26) A NEW FIRE HYDRANT APPEARS
 TO BE LOCATED NEW THE NEW
 TRANSFORMERS BUT COULD NOT
 LOCATE A CALL-OUT FOR IT ON THE
 PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910