2004-11-15 00:00:00 | ************* UNSAT ************* |
| |
| 1)NOTE: PLEASE SEE 230.95, 240.13 FOR |
| REQUIRED GFI PROTECTION OF MDP. |
| |
| 2)NOTE: PLEASE VERIFY/NOTE GROUNDING |
| ATTACHEMENTS FOR TRANSFORMER ON RISER. |
| WIRE AND CONDUIT SCHEDULE MENTIONS |
| CONDUCTOR SIZE ONLY. |
| 250.30 |
| |
| 3)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| BE THE UTILITY OWNED TRANSFORMER ON |
| RISER. IF FPL TRANSFORMER, THIS DOES NOT |
| NEED TO BE SHOWN. |
| THIS WORK WOULD BE DONE BY FPL AND NOT |
| FALL UNDER NEC. |
| NEC 90 |
| |
| 4)NOTE: PLEASE PROVIDE NOTE ON |
| ELECTRICAL RISER SHEET E2.1 FOR |
| REQUIREMENTS OF ELECTRICAL ROOM |
| /DOORS/HARDWARE PER 110.26 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2004-11-05 00:00:00 | IN FOR ELECTRICAL REVIEW. |
| ONE SET ONLY. |
| **** NOTES TO FOLLOW WHEN REVIEW IS |
| COMPLETE**** |
| FULL REVIEW NOT DONE AT THIS TIME. |