2004-11-24 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04100894 |
| ADD: 2600 N MILITARY TRL |
| CONT: THE WEITZ CO. |
| TEL: (561)723-5976 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| 1)PROVIDE NOC RECORDED WITH THE CLERK |
| OF |
| COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY |
| OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| SRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL |
| INSPEC |
| TION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING |
| AGEN- |
| CY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A |
| THRESH- |
| OLD BUILDING. THE PURPOSE OF THE |
| SRUCTUR |
| AL INSPECTION PLAN IS TO PROVIDE |
| SPECIF- |
| IC INSPECTION PROCEDURES AND SCHEDULES |
| SO THAT THE BUILDING CAN BE ADEQUATELY |
| INSPECTED FOR COMPLIANCE WITH THE |
| PERMITTED DOCUMENTS. |
| |
| 3)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 4) W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS |
| FOR THE BUILDING WHICH ARE REQUIRED TO |
| BE SIGNED AND SEALED BY THE ARCHITECT |
| OR |
| ENGINEER OF RECORD CON- TAIN A |
| STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR |
| ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 5) PROVIDE FLOOD ZONE ELEVATION |
| CERTIFICATE FOR NEW CONSTRUTION WITH |
| BASE FLOOD ELEVATION, CITY CODE |
| REQUIRES |
| AN ADDITIONAL 6".A-8, ELE 16.5'. |
| |
| 6)FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN |
| QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE |
| EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| PLAANS, SPECIFICATIONS REPORTS OR |
| OTHER DOCUMENTS PREPARED BY A |
| PROFESSIONAL ENGINEER AND BEING FILED |
| FOR PUBLIC RECORD SHALL HAVE THE |
| SIGNATURE AND THE SEAL OF THE DESIGN |
| PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ST S 61G15-23.002 ENGINEERS |
| |
| 7) SHEET S-5.3 CODES & STANDARDS 1-A, |
| TABLE 1606 IMPORTANCE FACTOR, BUILDINGS |
| OR STRUCTURES WITH OCCUPANT LOADS |
| GREATER THAN 300 IN A SINGLE ROOOM, THE |
| IMPORTANCE FACTOR SHALL BE 1.15, |
| BUILDING CATEGORY III. |
| |
| 8) SP-2 THE HANDICAPPED ENTRANCE VS THE |
| |
| MAIN ENTRANCE, THE ACCISSIBLE ROUTE |
| SHOULD BE THE SAME ROUTE TO THE MAXIMUM |
| EXTENT USED BY THE GENERAL PUBLIC, SEE |
| 11-4.3.2(1). |
| |
| 9) SHEET A1.1/A6.1 RETRACTABLE BENCHES, |
| THEY DO SHOW COMPANION SEATING BUT NO |
| INFORMATION AS TO HOW TO COMPLY WITH |
| VERTICAL ACCESSIBILITY. 11-4.1.2 |
| VERTICAL ACCESSIBILITY, NOTHING IN THIS |
| CODE SHALL BE CONSTRUED TO RELIEVE THE |
| OWNER OF ANY BUILDING, SSTRUCTURE OR |
| FACILITY FROM THE DUTY TO PROVIDE |
| VERTICAL ACCESSIBILITY TO ALL LEVELS |
| ABOVE OR BELOW THE OCCUPIAABLE GRADE |
| LEVEL. IF NOT SUPPLYING A LIFT AND |
| COMPANION SEATING TO ALL LEVELS, APPLY |
| TO THE STATE FOR A WAIVER. |
| |
| 10) SHEET A2.1 DOORS 127, 128& 129 THE |
| DOOR SCHEDULE INDICATES A FRAME TYPE"6" |
| FOR A 6'-0" WIDE SET OF DOORS, WHERE |
| ITSHOULD READ A 3'-0" DOOR WITH SIDE |
| LIGHT. THE SCHEDULE INDICATES THE 3'-0" |
| |
| FRAME WITH SIDELIGHT THERE IS ONLY 16" |
| ON THE LATCH SIDE OF THE DOORWAY WHERE |
| 18" IS REQUIRED, SEE 11-4.13.6. |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING |
| CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 11) SHEET A2.1/ A2.2 DOORS IN SERIES |
| SEE |
| 11-4.13.7. DOORS 164A&B, 159A&B, 154A&B |
| AND DOOR 151A&B. |
| |
| 12) SEE A2.1/ A2.2 VARIOUS STORAGE ROOM |
| & MECHANICAL ROOM DOORS SWING OUT INTO |
| THE COORIDOR, SEE 1021.4 DOORS THAT |
| SWING INTO AN EXIT ACCESS COORIDOR |
| SHALL |
| BE RECESSED TO PREVENT INTERFERENCE |
| WITH CORRIDOR TRAFFIC; ANY DOORS NOT |
| RECESSED SHALL OPEN 180 DEGREES TO STOP |
| AGAINST THE WALL. |
| |
| 13) A2.2 ROOM 141/142 THERE IS A LINE |
| DOWN THE CENTER OF THIS ROOM BUT NO |
| INFORMATION AS TO TYPE OF WALL. THIS |
| ROOM TO BE USED AS A WEIGHT/ FITNESS |
| ROOM WITH NO EQUIPMENT SHOWN ON PLANS |
| WILL HAVE A OCC LOAD OF 136 OCC LOAD. |
| THIS WILL REQUIRE 2 EXITS 1/2 THE |
| DIAGONAL APART UNSPRINKLERED, 1/3RD |
| THE DIAGONAL(MINIMAL) FOR SPRINKLERED |
| BLDGS. |
| |
| 14) A2.1 CLASSROOM 123 VS OFFICE |
| 115/116 |
| SINCE THERE IS A MIXED OCCUPANCY, TABLE |
| |
| 704.1 INDICATES A 2HR WALL BE BETWEEN |
| THESE OCCUPANCIES. |
| |
| 15) A2.1 CORRIDORS 130, 122, 165 & 148 |
| ALL INDICATE THE USE OF A TYPE (3) WALL |
| SYSTEM, THIS UL- U404 INDICATES A 1HR |
| AND A 2HR WALL. THE DETAIL ONLY |
| PROVIDES |
| |
| THE INFORMATION FOR THE 1 HR WALL. |
| PROVIDE THE INFORMATION FOR A 2 HR |
| RATING? |
| |
| 16) A2.1 ADDITIONAL INFO REQUIRED, |
| NO RATING FOR THE WALL BETWEEN THE |
| ENTRY |
| 126AND THE STUDENT LOUNGE? |
| |
| 17) THE SAME WALL LISTED ABOVE, PROVIDE |
| THE SEAL TO THE ROOF DECK ABOVE: |
| 705.7.1 JOINTS INSTALLED IN OR BE- |
| TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| TANT FLOORS OR FLOOR/ CEILING |
| ASSEMBLIES |
| AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| APPROVED FIRE RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE |
| FOR A PERIOD NOT LESS THAN THE RE- |
| QUIRED FIRE RESISTANCE RATING OF THE |
| WALL, FLOOR OR FLOOR IN OR BETWEEN |
| WHICH IT IS INSTALLED. |
| |
| |
| 18) 704.2.1.4 CORRIDOR PARTITIONS, |
| SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO |
| THE |
| AUTHORITY HAVING JURISDICTION. SUCH |
| IDEN |
| TIFICATION SHALL BE ABOVE ANY |
| DECORATIVE |
| CEILING CEILING AND IN CONCEALED |
| SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 19) A3.1 DOOR SCHEDULE, THE DOOR |
| SCHEDULE INDICATES THE USE OF "B" LABEL |
| DOORS, SEE TABLE 705.1.2 OPENING |
| PROTECTIVES ARE LABELED IN MINUTES AND |
| HRS. |
| |
| 20) 8A.3 DETAILS 1&4, THESE DETAILS DO |
| NOT INDICATE HOW THE WINDOW WALL IS TO |
| BE ATTACHED TO THE HORIZONTAL STEEL |
| FRAMING MEMBER. |
| |
| 21) A8.3 DETAIL 3 DOES INDICATE THERE |
| SHALL BE FASTENERS BUT WHAT TYPE OF |
| FASTENER AND SPACING. |
| |
| 22) A8.3 DETAIL 2 INDICATES THE USE OF |
| " BUTT GLAZING" SEE SECTION FBC 2406.2. |
| |
| 23) A8.3 DETAIL (1) IS MISSING |
| INFORMATION ON HOW THE STUCCO FRIEZE |
| ABOVE THE GLASS WALL (LOBBY) IS TO BE |
| BUILT, NO INFORMATION IS FOUND ON THE |
| STRUCTURAL SHEETS. |
| |
| 24) A8.3 DETAIL 4 NEEDS ADDITIONAL |
| INFORMATION, MISSING WIRE LATH WEIGHT, |
| "C" CHANNEL SPACING AND STEEL CEILING |
| JOIST (METAL STUDS) WEIGHT AND SIZE. |
| |
| 25) A7.5 INDICATES THE TERM "METAL STUDS |
| AS NECESSARY TO SUPPORT DRYWALL |
| CEILING", PLEASE PROVIDE THE ALLOWABLE |
| CEILING SPAN DEFLECTION, PSF, IF MIDSPAN |
| IS TO BE SUPPORTED, SIZE OF STUD AND |
| THICKNESS AND JOIST SPACING. |
| |
| THIS REVIEW WILL CONTINUE UNDER A |
| SECOND |
| BUILDING SESSION. |
| |
| SPACING |
| GLAZING" |