Plan Review Notes
Plan Review Notes For Permit 04100753
Permit Number 04100753
Review Stop E
Sequence Number 4
Notes
Date Text
2006-08-06 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE SEE PLANS SHOUDL STATE: DRAWN BY:
 AND SO ON.
 FBC 106.1.2 2004
 FBC 104.2.1 2001
  
 2) NOTE: PLEASE SEE WHIRLPOOL/JACUZZI
 TUB SHALL INDICATE THE REQUIRED GFI
 PROTECTION PER 680.71 EITHER BY BRKR OR
 DEVICE.
  
 3) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE AS A RECEPT IS BEING SHOWN W/OUT
 SYMBOL FOR GFI PROTECTION.
 210.8A6
  
 4) NOTE: PLEASE SEE DISHWASHER DISPOSAL
 IS BEING SHOWN WITH TWO SEPARATE
 DEVICE/RECEPTS ON PLANS , YET FED BY A
 2-POLE BRKR.
 210.4
  
 5) NOTE: PLEASE STATE THE 2002
 NFPA-70(NEC) ON PLANS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.