Plan Review Notes
Plan Review Notes For Permit 04100753
Permit Number 04100753
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-15 00:00:00******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1, OK, TITLE BLOCK FOR
 JOHN AVERCAMP REMOVED.
  
 2)NOTE: NOTE #2 NO.
 SUBMIT AIC RATING S FOR MAINS/ SERVICE
 PER 110.9/215.5
  
 3)NOTE: NOTE #3 OK.
 NOTED ON PLANS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE BOTH
 BATHS AND GEN LTS FOR BATHS ARE SHOWN ON
 SAME CIRCUIT.
 PLEASE SEE 210.52D,210.11C3
  
 5)NOTE: NOTE #5, OK.
 MOVED SD'S.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE
 IRRIGATION PUMP STILL SHOWS 30A OCP ON
 #12 AWG.
 PLEASE SEE OTHER ITEMS WERE REVISED.
  
 7)NOTE: NOTE #7 #8 AND #9 OK.
  
 8)NOTE: NOTE#10 NO. NOTE ADDED FOR ARC
 FAULT PROTECTION, HOWEVER PLEASE SEE
 NOTE # 6 ON ELECTRICAL NOTES.
  
 11)NOTE: NOTE #11, YES/NO, PLEASE SEE
 DISC WERE ADDED HOWEVER, MANUFACTURE
 SPECS NOT SUBMITTED.
 PLEASE SUBMIT SPECS SHOWING LISTING FROM
 A NRTL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  