2005-02-28 00:00:00 | CHECKLIST: |
| 1- DRAWINGS NEED PALM BEACH COUNTY |
| IMPACT FEES STAMP. ALSO, PAID RECEIPT |
| SAYS THERE IS $3.00 BALANCE DUE. CLARIFY |
| AND BRING BACK STAMPED DRAWINGS AND PAID |
| IN FULL RECEIPT. |
| |
| 2-A) ENTRY PORCH ON SHEET 6/10 CALLS FOR |
| CONCRETE BEAMS, WHILE, ROOF FRAMING PLAN |
| AND PORCH DETAILS CALL FOR WOOD BEAMS. |
| REVISE AS REQUIRED. |
| |
| B) ENTRY PORCH IN ROOF FRAMING PLAN |
| SHOWS 3-2X12 BEAM WHILE PORCH DETAIL ON |
| SHEET 8/10 SHOWS 2-2X12 BEAM. REVISE AS |
| REQUIRED. |
| |
| 3- SPECIFY HOW IS CANTILEVERED BEAM AT |
| NOOK AREA ANCHORED TO THE SIDE COLUMNS. |
| SPECIFY REINFORCING. SEC. 104.2.1.2 OF |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 4- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) ENTRY DOORS WITH DRAWINGS THAT MATCH |
| FLORIDA PRODUCT APPROVAL INFORMATION. |
| DRAWINGS SUBMITTED ARE FOR "BENCHMARK". |
| NEED DRAWINGS FOR "THERMA-TRU" MODELS AS |
| SPECIFIED ON FLORIDA PRODUCT APPROVAL |
| #1170 SUBMITTED. |
| |
| B) DOOR WITH SIDELITES AS SHOWN ON PLANS |
| |
| C) 45 DEGREES FIXED WINDOW COMPLETE |
| SYSTEMAS SHOWN ON NOOK AREA. |
| |
| D) GARAGE SIDE DOOR. |
| |
| 5- STORM SHUTTERS: A) CLEARLY MARK ON |
| DRAWINGS SPECIFIC MOUNTING CONDITIONS |
| AND ANCHOR TYPE AND SPACING TO BE USED. |
| CLEARLY MARK INSTALLATION SCHEDULE |
| INSIDE ENGINEERED DRAWINGS TO VERIFY |
| ANCHOR TYPE AND SPACING USED. |
| **NOTE; SEE PLANS FOR ENGINEER'S |
| CALCULATED DESIGN PRESSURES AT OPENINGS. |
| VERIFY STRUCTURE TO BE ATTACHED TO: 3000 |
| PSI CONCRETE OR MASONRY. |
| SEC. 104.2.1.2 CITY AMENDMETNS TO FBC. |
| B) CLEARLY INDICATE TYPE OF SHUTTERS |
| USED. 22 OR 24 GAUGE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |