Plan Review Notes
Plan Review Notes For Permit 04100753
Permit Number 04100753
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 5 SANITARY RISER DIAGRAM DOES NOT
 MEET THE CODE REQUIREMENTS, NOR DOES IF
 RELEECT THE FLOOR PLAN. SECTION
 104.2.1.
 A) KITCHEN SINK IS NOT VENTED. SECTION
 902.1.
 B) WASH MACHINE IS NOT VENTED, REQUIRES
 A STADPIPE, AND THE CLEANOUT SHALL BE
 INSTALLED 4 FT. ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 902.1, 1002.1, &
 708.10
 C) MASTER BATH SHOWS 2 SHOWERE ON THE
 SANT. RISER DIAGRAM, BUT ONLY ONE ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 D) BATH #2 IS SHOWN AS CONNECTING TO
 THE BLDG DRAIN DOWNSTREAM OF THE
 KITCHEN, WASH MACHINE, AND MASTER BATH
 ON THE RISER DIATRAM, BUT UPSTREAM OF
 THESE FIXTURES ON THE FLOOR PLAN. PLEASE
 SHOW THE RISER AS IT WILL BE INSTALLED.
 SECTION 104.2.1.
  
 2) SEE ATTACHED SHEET SHOWING AN EXAMPLE
 OF A SANITARY RISER DIAGRAM THAT MEETS
 THE CODE REQUIREMENTS AND REFLECT THE
 FLOOR PLAN.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]